INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-411A
2 - 5
NKTU02, NKTU12 AND NKTM01 CABLES
This cable connects the IDO termination module to a master or
slave module. To install the cable:
1. Pull the master or slave module out several inches from the
MMU backplane.
2. If round type cables are already installed in the termination
mounting unit, remove the cable retaining bracket.
3. Insert the J2 end (use either end of the NKTM01 cable) of
the NKTU02 or NKTU12 cable into the MMU backplane slot
assigned to the master or slave module. The cable should latch
securely into place. Card edge connector P3 of the master or
slave module connects to this end of the cable.
4. Connect the shield wire extending from the J2 end of the
NKTU02 or NKTU12 cable to the shield bus bar.
5. Insert the J1 end (use the remaining end of the NKTM01
cable) of the NKTU01 or NKTU12 cable into the termination
mounting unit backplane slot assigned to the IDO module. The
cable should latch securely into place. Card edge connector P1
of the IDO module connects to this end of the cable.
6. Insert the master or slave module into the MMU until it
locks into place.
7. Replace or add the cable retaining bracket if round type
cables are installed in the termination mounting unit.
Installing the Termination Module
The IDO module inserts into the termination mounting unit
and occupies one slot. To install:
NOTE: Ensure all jumpers are configured prior to installation.
1. Verify the slot assignment of the IDO module.
2. Align the IDO module with the guide rails in the termina-
tion mounting unit and partially insert the module.