IMDSM05 DIGITAL I/O SLAVE MODULE CONFIGURATION
INTRODUCTION
A - 2
I-E96-411A
®
type (jumpers J1 through J16), and master module type (jump-
ers J17 and J18). Refer to the
IMDSM05 Digital I/O Slave
Module
instruction manual for detailed instructions.
Table A-2. Switch S2 Settings
Switch Position
1 - 8
Function
1
An output signal will be sent to the Group B output
point corresponding to the switch position number
during default conditions.
0
No output signal will be sent during default.
NOTE: 0 = closed or ON, 1 = open or OFF.
Table A-3. Switch S3 Settings
Switch
Position
Function^
1
2
3
4
1
0
Set group A I/O points to outputs.
Set group A I/O points to inputs.
1
0
Set group B I/O points to outputs.
Set group B I/O points to inputs.
1
0
Module is an interface between a master module and a
digital logic station (switch positions 1 and 2 must be set
to 1, switch position 4 must be set to 0, switch position 8
of switch S2 must be set to 0).
Module is an I/O interface between a master module and
field devices.
1
0
All outputs hold on master module failure.
All outputs go to default value on master module failure.
NOTE: 0 = closed or ON, 1 = open or OFF.
Table A-4. Example Switch S4 Settings
Address
Example
Switch Position
(Binary Value)
1
(128)
2
(64)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(2)
0
0
0
0
0
0
0
0
0
16
0
0
0
1
0
0
0
0
32
0
0
1
0
0
0
0
0
48
0
0
1
1
0
0
0
0
63
0
0
1
1
1
1
1
1
NOTE: 0 = closed or ON, 1 = open or OFF.