TROUBLESHOOTING
MODULE STATUS SUMMARY
5 - 12
WBPEEUI230019A0
®
Bytes 3 through 5
(continued)
3
4
5
02
00
04
02
00
05
Analog input reference error:
1 V reference
5 V reference
03
<X>
2
<Y>
2
Missing I/O module:
XY = block no.
05
<X>
2
<Y>
2
Configuration error - undefined input:
X = block no. making reference
Y = block no. being referenced
06
<X>
2
<Y>
2
Configuration error - data type match:
X = block no. making reference
Y = block no. being referenced
08
<X>
2
<Y>
2
Trip block activated:
X = block no. of trip block
Y = block no. making reference
0F
—
—
The primary MFP module has failed and the redundant
MFP module configuration is not current.
10
—
—
The primary MFP module has failed and the SRAM data in
the redundant MFP module is not current.
Byte 6
—
Extended module type:
24 = IMMFP01/IMMFP12/IMMFP03
Byte 7
CWA
—
Controlway bus A (80 = failure)
CWB
—
Controlway bus B (40 = failure)
Byte 14
—
Nomenclature:
01 = IMMFP01
02 = IMMFP12
03 = IMMFP03
Byte 15
—
Revision letter
(ASCII letter)
Byte 16
—
Revision number
(ASCII digit)
NOTES:
1.These fields are expressed in binary format.
2.All block numbers are expressed in BCD.
3.All fields listed in this table are expressed in hexadecimal format unless otherwise specified.
Table 5-10. Field Descriptions of the IMMFP12 Module Status Report
(continued)
Field
Value
Description