TROUBLESHOOTING
MODULE STATUS SUMMARY
WBPEEUI230019A0
5 - 11
Table 5-9. IMMFP12 Module Status Report
Byte
Bit
7
6
5
4
3
2
1
0
1
ES
MODE
MODULE TYPE
2
FTX
BAC
RIO
LIO
CFG
NVF
NVI
DSS
3
Bytes 3-5 combine to define other errors.
1
4
5
6
Extended module type = 24
7
CWA
CWB
8 - 13
Unused
14
Nomenclature (decimal digit)
15
Firmware revision level (ASCII letter)
16
Firmware revision level (ASCII digit)
NOTE: 1. Refer to Table
Table 5-10. Field Descriptions of the IMMFP12 Module Status Report
Field
Value
Description
Byte 1
ES
—
Error summary (0 = good, 1 = errors)
1
MODE
—
Module mode (00 = configuration, 01 = error, 11 = execute)
1
MODULE TYPE
—
Module type code (15 = enhanced status)
Byte 2
FTX
—
First time in execute (0 = no, 1 = yes)
1
BAC
—
Backup MFP status (0 = good, 1 = bad)
1
RIO
—
Summary remote I/O status (0 = good, 1 = bad)
1
LIO
—
Summary local I/O status (0 = good, 1 = bad)
1
CFG
—
On-line configuration changes being made (0 = no, 1 =
yes)
1
NVF
—
NVRAM checksum error (0 = good, 1 = bad)
1
NVI
—
NVRAM default configuration (0 = no, 1 = yes)
1
DSS
—
Digital station status (0 = good, 1 = bad)
1
Bytes 3 through 5
3
4
5
01
01
—
01
02
—
01
03
—
01
FA
—
01
FF
—
NVRAM error:
Write failure
Checksum failure
Bad data
Reset during SP write
Reset during write