INTRODUCTION
WBPEEUI230019A0
5 - 1
SECTION 5 - TROUBLESHOOTING
INTRODUCTION
This section contains information on the LED error codes, mis-
cellaneous LED states, and diagnostic functions. Table
lists MFP module error codes, their meaning, and possible cor-
rective actions. Table
lists all other possible LED states.
The flowcharts in Figures
provide a quick refer-
ence guide to the front panel error codes and possible correc-
tive actions.
Table 5-1. IMMFP12 Module Error Codes
Code
LED
8
7
6
5
4
3
2
1
Condition
Corrective Action
01
0
0
0
0
0
0
0
1
NVRAM memory
checksum error
Initialize NVRAM. If error recurs,
replace the MFP module. If error recurs
call Elsag Bailey field service.
02
0
0
0
0
0
0
1
0
Analog input calibration
error
Check status bytes 4 and 5 of your
IMCIS02, IMASO01, or IMASO03 mod-
ule for an invalid reference.
03
0
0
0
0
0
0
1
1
Auxiliary module status
bad
Check the status bytes of the auxiliary
module for more information.
05
0
0
0
0
0
1
0
1
Configuration error
(undefined block is
referenced)
Check the configuration for any faulty
block references and correct any
found. Execute the configuration after
making the corrections.
06
0
0
0
0
0
1
1
0
Configuration error (data
type mismatch)
Check the configuration for any com-
mand referencing an invalid data type.
Execute the configuration after making
the corrections.
08
0
0
0
0
1
0
0
0
Trip block activated
Review the configuration to determine
why the TRIP function code in the con-
figuration has stopped the MFP mod-
ule.
0B
0
0
0
0
1
0
1
1
NVRAM memory
initialized
Confirm that NVRAM is initialized; no
action is required.
0C
0
0
0
0
1
1
0
0
NVRAM memory opened
for write operation
Initialize the NVRAM memory. If the
error recurs, replace the MFP module.
If error recurs call Elsag Bailey field
service.
0D
0
0
0
0
1
1
0
1
Redundancy link
communication error
Check the cable connection between
primary and secondary MFP modules.
Check the cable connection from MFP
module to the termination unit or mod-
ule.
0E
0
0
0
0
1
1
1
0
Redundant module IDs
are the same
Place pole 8 of dipswitch SW4 in the
opposite position of dipswitch SW4
pole 8 of the primary module.