TROUBLESHOOTING
DIAGNOSTICS
5 - 6
WBPEEUI230019A0
®
DIAGNOSTICS
The IMMFP12 Multi-Function Processor Module firmware con-
tains diagnostic tests that can be invoked during module
power-up. Putting the MFP module into the diagnostic mode
allows the module to perform a variety of diagnostic tests but
suspends normal operation. The diagnostic tests allow verifica-
tion of the module components and circuitry. This section
describes each diagnostic test and how to use it.
Overview
Select the required diagnostic test using the MFP module
dipswitches. LEDs one through eight display the results of the
test. Both group and individual tests can be executed.
Table 5-4. IMMFP12 Connector P2 Pin Assignments
Pin
Signal
Pin
Signal
1
Data Bit 1
2
Data Bit 0
3
Data Bit 3
4
Data Bit 2
5
Data Bit 5
6
Data Bit 4
7
Data Bit 7
8
Data Bit 6
9
Bus Clock
10
Synchronization
11
Reserved
12
Reserved
NOTE: All data bits are true low.
Table 5-5. IMMFP12 Connector P3 Pin Assignments
Pin
Signal
Pin
Signal
1
DCS A (-)
16
DCS A (+)
2
DCS B (-)
17
DCS B (+)
3
Redundancy Transmit (-)
18
Redundancy Transmit (+)
4
Redundancy Transmit
Clock (-)
19
Redundancy Transmit
Clock (+)
5
Redundancy Receive (-)
20
Redundancy Receive (+)
6
Redundancy Receive
Clock (-)
21
Redundancy Receive
Clock (+)
7
Receive A (-)
22
Receive A (+)
8
Receive B (-)
23
Receive B (+)
9
Clear to Send A (-)
24
Clear to Send A (+)
10
Clear to Send B (-)
25
Clear to Send B (+)
11
Transmit A (-)
26
Transmit A (+)
12
Transmit B (-)
27
Transmit B (+)
13
Request to Send A (-)
28
Request to Send A (+)
14
Request to Send B (-)
29
Request to Send B (+)
15
Digital Output (+)
30
Digital Output (-)