INSTALLATION
SETUP AND PHYSICAL INSTALLATION
3 - 4
WBPEEUI230019A0
®
Dipswitch SW4 Settings
Dipswitch SW4 enables the selection of a variety of module
options. Refer to Table
for an explanation of the option set-
tings. Refer to
of this instruction for the diagnostic
dipswitch setting information.
NOTE: Poles one through seven on redundant MFP modules must
be set to the same values.
3
1
0
Controlway (1 Mbaud) mode.
1
Module bus (83.3 kbaud) mode.
4 - 8
2
2 - 31
Controlway or module bus address.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF; shaded areas designate mandatory pole settings.
1. Set jumper J5 for the same mode set by this dipswitch pole.
2. Address zero and one reserved whenever communication modules are used.
Table 3-2. Example IMMFP12 Module Address Settings
Address
Example
Dipswitch Position
(Binary Value)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
7
0
0
1
1
1
15
0
1
1
1
1
User
Setting
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-1. IMMFP12 Dipswitch SW3 Settings
Pole
Setting
Function
User
Setting
Table 3-3. IMMFP12 Dipswitch SW4 Normal Operation Settings
Pole
Setting
Function
User Setting
1
0
Disable special operations.
1
Enable special operations. Refer to
in this
section for explanation.
2
0
Disable on-line configuration.
1
Enable on-line configuration.
3
0
Perform NVRAM checksum routine.
1
Inhibit NVRAM checksum routine.
1
4
0
Perform ROM checksum routine.
1
Inhibit ROM checksum routine.
1
5
0
Reserved for future options. Use this setting for normal operations
even though it performs no function at this time.
1
Reserved for future options. Do not use this setting.