Table 5-21. Relay Setting Options
Options
When to Close the Associated Relay’s Contact
NEVER
Never
>= SETPOINT
If current reading is greater than or equal to the corresponding ALARM SETPOINT value
< SETPOINT
If current reading is less than the corresponding ALARM SETPOINT value
ON FAULT
If a fault occurs (see Fault Codes on page 78)
IN MEASURE
When the H25-IR PRO is in measure mode
AT LOG LIMIT
If the current reading reaches or exceeds the programmed LOG LIMIT value
SETUP 1 ON
User Setup #1 is active
SETUP 2 ON
User Setup #2 is active
SETUP 3 ON
User Setup #3 is active
SETUP 4 ON
User Setup #4 is active
IF TESTING
The relay is closed if the instrument is operating normally (Search or Measure modes).
The relay opens if the menu system is accessed or the instrument experiences a fault.
5.6.3. Measurement Log
The Measurement Log is a 50-element array that contains up to 50 log points that you choose. Each log point contains:
•
Log point number (e.g., 1 of 50, 2 of 50, etc.)
•
Date and time stamp when the log point was collected
•
Measured sample rate at that date and time
•
The total of all log data samples (used for totalization applications).
The user can scroll through the available data by using the Up Arrow and Down Arrow buttons. For additional information
on logging data, refer to Figure 5-8 on page43 and Table 5-5 on page 44.
NOTE:
Logging is only possible when the H25-IR PRO is in Measure mode.
NOTE:
Use the SETUP button to clear individual log points.
NOTE:
Use the MODE+SETUP button combination to clear the entire Measurement Log.
Summary of Contents for H25-IR PRO
Page 6: ...H25 IR PRO Instruction Manual vi P N 3015 5678 Rev 6 ...
Page 8: ...H25 IR PRO Instruction Manual viii P N 3015 5678 Rev 6 ...
Page 39: ...H25 IR PRO Instruction Manual Menu System Overview P N 3015 5678 Rev 6 29 ...
Page 109: ...H25 IR PRO Instruction Manual Maintenance P N 3015 5678 Rev 6 99 ...
Page 120: ...H25 IR PRO Instruction Manual Declaration of Conformity P N 3015 5678 Rev 6 110 ...