7.2.37
Alarm 49 – SPINDLE NOT ACTIVATED
ALARM 49 – SPINDLE NOT ACTIVATED
1 of 1
CONDITION / CHECK
DESCRIPTION
MALFUNCTION
Spindle start up attempt not activated.
POSSIBLE CAUSE
There are various possible causes:
Inverter off or in alarm state
Spindle-inverter connection problem
Inverter-PLC input connection problem
SOLUTION
Enable the ENABLE SPINDLE SK
In automatic, from programme, check the presence of the M3 code in
the piece programme (or in the MASTER)