background image

4

SUBJCET TO CHANGE WITHOUT PRIOR NOTICE

If transmission network interfaces are used, especially when cables are routed outside the building, use more protection 
against electrical interference.

In case of danger of frost, empty the system and, if necessary, remove the meter.

Rinse the pipes thoroughly before installing the meter.

The meter shall be installed in the direction of the arrow on the meter housing, corresponding to the direction of the flow.

Avoid collecting air bubbles in the meter during the installation process.

The meter shall not be subjected to mechanical stress when installed in the pipe.

The meter shall be installed in a way that it is protected from all external impurities and contamination.

Remove the old seals and clean the sealing surfaces.

Slightly grease the sealing surfaces (use grease approved for drinking water and acid-free).

The meter can only be installed in frost-proof areas.

Use only the gaskets supplied (the gaskets must not get into the pipe). Seals provided on site must be fit for purpose 

and comply with local guidelines and directives. No liability is accepted for consequential damage resulting from the use 

of third-party seals, such as corrosion of seal surfaces and threads.

Manually and simultaneously screw the meter fittings on both sides and then tighten in opposite 
directions using a suitable tool.

Slowly fill the pipe with water after installation.

The meter must be protected against pressure shocks in the pipe.

The table below presents troubleshooting procedures:

Error

Cause

Troubleshooting

Display off

Batteries may be damaged or discharged.

Notify the service department

Damaged casing

Possible external impact or fall to 

the ground

Lower case body separated 

by electronic unit

Tampering by third parties or strong 

external impacts

Open and visible electronic unit

Consumption is not accounted for

Tampering by third parties, strong external 

impacts or flow detection sensor damage

Do not transmit radio signal

Flow failure of 5 liters or the batteries may 

be damaged or discharged

Error ‘_ _ _ _ L Err’ present on display

Possible leakage in the water 

supply/plant/taps

Check for leakage in the water 

supply/system/tap

Error ‘_ _ _ _ O Err’ present on display

Range higher than Q4 for 10 

consecutive minutes

Error ‘_ _ _ _ I Err’ present on display

Continuous reverse flow greater 

than 20 liters

Installations requirements

All water meter versions can be installed both horizontally and vertically.

H

H

H

V

Summary of Contents for HYDROSONIC-M1

Page 1: ...Function 5 Display 5 3 Radio parameters 5 Delivery status 5 Operating mode Radio activation 5 4 Device display loop 6 5 Error message 7 6 Battery and replacement procedures 8 7 Information for correct...

Page 2: ...H mm 90 93 107 114 h mm 20 21 30 28 33 01 Serial number 02 Q3 meter size 03 Measuring class installation positioning allowed RxxH horizontal installation RxxVH vertical and horizontal installation 04...

Page 3: ...itable billing of consumption possible Carefully observe the instructions in the data sheet instruction manual application notes and lid Failure to comply with the operating conditions may result in s...

Page 4: ...ulting from the use of third party seals such as corrosion of seal surfaces and threads Manually and simultaneously screw the meter fittings on both sides and then tighten in opposite directions using...

Page 5: ...ng software Packet data will be transmitted according to the default or NFC settings If the frequency is 200 seconds the transmission is asynchronous otherwise synchronous Transmission frequency confi...

Page 6: ...icon on the display will flash every second If it succeeds the icon will remain fixed and stable otherwise it will turn off It is possible to change the configuration parameters via android NFC devic...

Page 7: ...Historical Day Date 2 not displayed by default 2 seconds CRC 32 ultrasonic firmware legal part 2 seconds Every 130 seconds the display will show the following reduced cycle If an error occurs an error...

Page 8: ...recorded END BATTERY LIFE Low battery Contact supplier NFC FRAUD n Continuous NFC field detected for several consecutive minutes Reset via NFC or LORA RTC P Sudden reset of date and time detected Upd...

Page 9: ...rrect disposal 8 Technical data Model HYDROSONIC M1 Metrological class R250 R400 R500 on request Flow detection technology Ultrasonic Temperature class T50 cold water from 0 1 C to 50 C Display LCD 8...

Page 10: ...O 4064 3 2017 EN 14154 3 2005 A2 2011 OIML R 49 3 2013 EN ISO 4064 5 2017 ETSI EN 300 220 2 v3 2 1 ETSI EN 300 220 1 v3 1 1 ETSI EN 301 489 3 v 2 1 1 ETSI EN 301 489 1 v2 2 3 Welmec Guide 7 2 2020 EN...