Azbil Corporation
Installation of this instrument
Model: MVC10A/10F - Multivariable Air Flow Meter 2-5
Note:
•
Before installing the flow meter, be sure to exercise flushing (cleaning the inside
of the pipe) to remove any foreign matter that may be present inside the pipe.
Residual foreign matter could cause output fluctuations.
•
Make sure the fluid flow direction matches the flow-direction indicating arrow
mark (
ð
) of the flow meter. Otherwise, stabilized output cannot be obtained.
Fig. 2-3
Examples of erroneous installations (1)
Note:
•
Never attempt to force the detector between the two piping flanges when the
space is too narrow. It can damage the instrument.
Fig. 2-4 Examples of erroneous installations (2)
Connection with remote type converter
When mounting the converter on a bracket, tighten the bolts and ensure that there is
no play. After mounting the converter, if the bolts for fixing the converter with the
bracket are loosened, tighten them again. (Bracket tightening torque: 40 N-m) When
mounting a tube included in the standard accessories, ensure that the following are in
order:
•
When cutting to a suitable length, the cut cross-section is clear.
•
When cutting a tube, ensure that the tube is not collapsed.
• The bend radius of the tube is not so small as 15 mm or less.
•
When mounting the tube on the fitting, ensure that it is securely pushed in.