Operation using the data setting device
Azbil Corporation
5-32
Model MCB10A
Set pulse scale in accordance with the following procedure:
Step
Procedure
Screen
1
Enter ENGINEERING MODE in accordance
with the entry into ENGINEERING MODE
(see section 5-4-10). Then press the
h
or
i
key to display the screen at right.
12.3 %
# PLS 27.780 Hz
100.00 l/p
SCL
2
Press the
g
key to move the cursor to the
position under a desired value to be set or
changed.
12.3 %
# PLS 27.780 Hz
100.00 l/p
SCL
3
Using the
h
or
i
key, change the value to a
desired pulse scale to be set.
12.3 %
# PLS 13.890 Hz
200.00 l/p
SCL
4
Press the
g
key to move the cursor to the
position under #.
Press the MODE key to return to the
MEASURING MDOE and to save data.
12.3 %
# PLS 13.890 Hz
200.00 l/p
SCL
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new
value before the system resets it to the previously saved value.