UMAX130511 Version 1.00A Preliminary Documentation
– May be subject to change
116 - 141
Access
RW
PDO Mapping
No
Value Range
0 (OFF) to 1 (ON)
Default Value
0 [OFF]
2.4.49. Object 3yz3h: LTyz X-Axis Decimal Digits PV
This object describes the number of digits following the decimal point (i.e. resolution) of the X-Axis input data
and the points in the lookup table. It should be set equal to the decimal digits used by the PV from the control
source/number as defined in Table 17.
Object Description
Index
3yz3h (where yz = 01 to 08)
Name
LTyz X-Axis Decimal Digits PV
Object Type
VARIABLE
Data Type
UNSIGNED8
Entry Description
Sub-Index
0h
Access
RW
PDO Mapping
No
Value Range
0 to 3
Default Value
0
2.4.50. Object 3yz4h: LTyz Y-Axis Decimal Digits PV
This object describes the number of digits following the decimal point (i.e. resolution) of the Y-Axis points in
the lookup table. When the Y-Axis output is going to be the input to another function block (i.e. an analog
output), it is recommended that this value be set equal to the decimal digits used by the block that is using
the lookup table as the control source/number.
Object Description
Index
3yz4h (where yz = 01 to 08)
Name
LTyz Y-Axis Decimal Digits PV
Object Type
VARIABLE
Data Type
UNSIGNED8
Entry Description
Sub-Index
0h
Access
RW
PDO Mapping
No
Value Range
0 to 3
Default Value
0