3.3.11 Object 7322h: AO Output Scaling 2 PV
This object defines the maximum value of the input, and should be specified to equal the
corresponding scaling object of the control source, as outlined in Table 7. It will be scaled
in the physical unit of the control source. The resolution will ALWAYS be dependent on
object 6302h AO Decimal Digits PV, even when the output is not being controlled directly
by the AO Output PV object 7300h. This object must always be larger than object 7322h
AO Output Scaling 2 PV.
Object Description
Index
7322h
Name
AO Output Scaling 2 PV
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h to 4h (x = 1 to 4)
Description
AOx Scaling 2 PV
Access
RW
PDO Mapping
No
Value Range
See Table 7
Default Value
5000 [mV]
3.3.12 Object 7323h: AO Output Scaling 2 FV
This object defines the output field value when the input data is at or above the AO Output
Scaling 2 PV value as shown in Figure 9. It will be scaled in the physical unit of the output,
dependent on range, with the resolution defined in object 6332h AO Decimal Digits FV.
The value can be set anywhere within the allowable output range as outlined in Table 4.
This value can be set lower than object 7321h AO Output Scaling 1 FV for an inverse
response (i.e. decreasing) to an increasing input.
Object Description
Index
7323h
Name
AO Output Scaling 2 FV
Object Type
ARRAY
Data Type
INTEGER16