Operation instructions | MIP 8-00 | MIP 16-00 | MIP 8-06 | MIP 16-06
Page 10 of 48
BA_MIP-8-16-0x.pdf | Technical improvements, changes in design, printing- and other errors reserved. | 2022-01-10
2.
Mounting and Installation
Installation must be performed by authorized and skilled electricians only.
Before mounting and installation, pull the mains plug (1)!
The antenna system must be installed and grounded according to the EN 60728-11 standard.
2.1.1.
Mounting in a 19“ rack
Note:
For 19-inch rack mounting, there must be at least 5 cm clearance in front of and behind the unit.
Slide the device into the 19 "rack.
Screw the device with four screws (1).
Observe the standard EN 60728-11.
2.2.
Equipotential bonding
The device must be connected to the equipotential bonding according to EN 60728-11. Use the equipotential bonding
connection at the device.
To connect the outer conductor of the coaxial cable to the equipotential bonding, use e.g. QEW earthing angles or CFA
earth connection blocks at the inputs and output (see 2.4 on page 11).
2.3.
Power supply
The devices are equipped with two redundant power supplies to connect them e.g. to different power sources (e.g. a normal
mains socket and a UPS). The LEDs show the status of the power supply.
If a power supply fails, the unit will start with an alarm tone. If you operate the device only with one power supply unit, you
can deactivate the alarm tone in the configuration ( see 5 on page 31). Alternatively, you can remove the unused power supply
from the device.
Connect both power supplies with the enclosed cables to 230 V AC. Open the pull-out protection, insert the plug of the
power supply unit and secure it with the pull-out protection.
Lights green when
operating voltage OK.
Flashes red when
voltage fails.