REV03016730010220
19
•
Auto Water Drain Float Switch (
If Applicable
)
- Manually raise the “HIGH” float switch located on the Auto
Water Drain’s Water Collection Drum. An alarm should be indicated on the System Controller. Reset the alarm by
pushing the Alarm Reset button on the enclosure door panel.
•
Tank Overflow (
If Applicable
)
– Manually raise the “HIGH” float switch located on each of the connected tanks.
The pump should immediately turn off and the “Tank Overflow” alarm should be indicated on the System
Controller. Reset the alarm by pushing the Alarm Reset button on the enclosure door panel.
Note: If any of the above described alarm test procedures fail or if any alarm trip value deviates, immediately contact AXI
International.
Summary of Contents for STS 6030
Page 2: ...REV03016730010220 1 ...