REV03016730010220
9
7.
After injecting the desired amount of additive, close the Injection Port Ball Valve and return the System Ball Valve
to the fully open position
Auto Additive Injection –
If Applicable
1.
To start Auto Additive Injection, navigate from the Main Menu to the Additive Injection screen on the HMI.
2.
On the screen there are two fields to input information, Gallons to Treat and Treatment Ratio.
3.
There are two other non-editable fields that show the last treatment date and also the amount of additive that was
added from the last treatment.
4.
Enter the gallons of fuel to treat.
5.
Then enter the treatment ratio (For example: 5 Gallon Jug of AFC treats 25,000 gallons of fuel, so enter 1:5000)
6.
Once this information is entered, press the START button to begin the injection process.
7.
There is a progress bar that will display the total amount of additive to be added (full red bar), and as the additive
is injected the red bar will decrease.
8.
Once the bar is depleted, the process will stop.
9.
If at any point the process needs to be manually stopped, press STOP on the screen.
10.
After the injection is completed, the data is stored in the log, which can be accessed by pressing LOG on the
Additive Injection screen.
11.
When the additive level reaches low, a “LOW ADDITIVE WARNING” will be displayed.
12.
In order to run the process again, the additive must be refilled and the alarm reset by clearing all alarms.