General Overview
STS 6030 | 7030 Specifications
Nominal Flow Rate…………………………………………….. 30 GPM/1,800 GPH (113.6 LPM/6,813.7 LPH)
14,400 gallons (54,510 liters) per 8-hour shift
43,200 gallons (163,530 liters) per 24-hour shift
Primary Filter…………………………………………………… 1, 5, 10, or 25
μ
Particulate or Water Block Filter Element
Secondary Filter.………………………………………………. 1, 5, 10, or 25
μ
Coalescing Filter Element
Fuel Conditioner……………………………………………….. LG-X 4000 Inline Magnetic Conditioner
Strainer………………………………………………………….. 20 Mesh Wye-Strainer
Plumbing………………………………………………………... Black Iron
Inlet Port………………………………………………………… 2” NPT
Outlet Port…….………………………………………………… 1.5” NPT
System Enclosure……………………………………………... NEMA 4 Rated Powder Coated or NEMA 4X Rated Stainless
Steel
Operating Temperature (6000 Series)………………………. 41 - 104°F (5 - 40°C
)
Operating Temperature (7000 Series)………………………. 41 - 122°F (5 - 50°C
)
Electrical………………………………………………………... 480V/60Hz/15A/1Ph or 230V/50Hz/15A/1Ph*
Pump………………………………………………………….… 2 HP Spur Gear Pump
Suction Capability (Primed)……………………………….….. 15ft. vertical lift or 100ft. horizontal run (lines >1.5”, primed)
Timer…………………………………………………………....
Incorporated PLC-based timer
Maximum Fluid Viscosity……………………………………..
5 cSt
Outline Dimensions………………………………..…………..
≈
56” x 72” x 17” (142 x 183 x 43 cm) (H x W x D)
System Weight…………………………………………………
≈
760 lbs (345 kg)
*Note: It is the user’s responsibility to ensure safe operating conditions for the system to be ran.
*At 50 Hz., nominal flow rate decreases from 30 GPM/1,800 GPH to 24 GPM/1,440 GPH.
!WARNING! This system is not meant for use with gasoline or any other flammable liquids having a flash point
less than 100°F (37.8° C). Use with gasoline or any flammable liquids at a temperature exceeding their flash point
presents an immediate explosion and fire hazard.