REV03016730010220
21
14.
Leaving the vent valve open to allow air to escape while the unit completely fills.
15.
When a small amount of fluid flows out of the vent, close the vent valve tightly.
16.
Push the Alarm Reset button on the enclosure door panel to acknowledge the alarm and reset it.
17.
Return the enclosure door panel selector switch to its original position.
18.
Check for leaks when re-starting and pressurizing the system.
Note: Disposal of fuel, associated waste, and filters must be in accordance with all applicable federal, state, and local
rules, laws, standards, and regulations.
!WARNING!: Some fuels may have been treated with biocides. Biocides are extremely toxic and may enter the
body through the skin. It is recommended to use adequate protection and proper precautions if the fuel at-hand
contains biocide type products.
Replacement Filter Chart
STS SERIES FILTERS
All Filters are absolute, unless otherwise noted | wb: waterblock | SS: Stainless Steel Screen
Primary Cartridge Filters
1
µ
5
µ
10
µ
25
µ
Particulate
FBO-60339
FBO-60340
FBO-60357
FBO-60341
Water block
FBO-60342
FBO-60343
FBO-60358
FBO-60344
Seconrdary Cartridge Filters
1
µ
5
µ
10
µ
25
µ
Coalescing
FBO-60336
FBO-60337
FBO-60356
FBO-60338
Servicing the Wye-Strainer
Excessive debris in the Wye-Strainer will result in a pump shutdown and “High Vacuum” alarm. This indicates that it is
time to clean the strainer basket.
Servicing the Wye-Strainer:
1.
Turn the enclosure door panel selector switch to the “OFF” position – making sure the pump will not turn on.
2.
Close the inlet and outlet ball valves.
3.
Place an appropriate container below the drain valve bottom of the Wye-Strainer
4.
Open the drain valve and allow all fluid to drain from the Strainer
5.
Using an adjustable wrench, unscrew the cap on the bottom of the Strainer
6.
Remove the strainer basket, clean, and replace
7.
Replace the cap on the bottom of the Strainer and tighten securely
8.
Close the drain valve
9.
Open the inlet and outlet ball valves.
10.
Push the Alarm Reset button on the enclosure door panel to acknowledge the alarm and reset it.
11.
Return the enclosure door panel selector switch to its original position.
12.
Check for leaks when re-starting and pressurizing the system.
Auto Water Drain (AWD) –
If Applicable
Servicing Auto Water Drain Strainer:
1.
Turn the enclosure door panel selector switch to the “OFF” position – making sure the pump will not turn on.
2.
Close the system’s Inlet and Outlet Isolation Ball Valves.
3.
Place a fuel waste container below the strainer and Manual Drain Port.
4.
Ensure the AWD’s Isolation Ball Valve is closed by opening the Manual Drain Port.
5.
Open the bleed screw on top of the Filter Housing to break vacuum.
Summary of Contents for STS 6030