Installing the DeviceNet
Base Controller
Installation and
Safety Guidelines
2–6
Installing the T1K–DEVNETS Base Controller
Disable I/O Polling Diagnostics *
I/O Diagnostics
SW 4
Enable
OFF
Disable
ON
*
If DIP Switch 4 is in the OFF (default) position, you must allow for two additional
bytes on the input (RX) and two additional bytes on the output (TX) for Terminator I/O
diagnostic functions. Refer to page B–6 for the I/O diagnostic information.
Hold Outputs
Maintenance Port Baud
Rate
Maintenance Port
Protocol Selection
Outputs
SW5
Baud Rate
SW 6
Protocol
SW7
Turn Off
OFF
9600 bps
OFF
Normal
OFF
Hold
ON
19200 bps
ON
ASCII
ON
Maintenance Port RTS/CTS Control
SW 8
RTS/CTS
Description
OFF
Disable
RTS/CTS not available
ON
Enable
RTS/CTS available
Setting up the parameters of the T1K–DEVNETS will set the values to special
registers when power is applied to it. When the registers are set to the correct range,
their parameters will be stored in EEPROM, and the parameters will be retained
when power is turned off. Refer to the following table.
Parameter Table
System
V–Memory
Description
Value when the scratch
pad is initialized
Range
V7614
Input register:
Starting location
V3000
V0 – V7377
V7615
Input Register:
Number of bytes
58 Bytes
0 – 128
V7616
Output Register:
Starting location
V3100
V0 – V7377
V7617
Output Register:
Number of bytes
52 Bytes
0 – 128
T1K–DEVNETS
setup parameters
Summary of Contents for T1K-DEVNETS
Page 2: ...T1K DEVNETS DeviceNet Base Controller User Manual Manual Number T1K DEVNETS M...
Page 25: ...1A Specifications In This Appendix Specifications...
Page 28: ...1B Tables In This Appendix DeviceNet Tables...
Page 35: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Page 43: ...1D T1K DEVNETS Think Do Setup In This Appendix T1K DEVNETS T D Setup...
Page 46: ...1 E T1K DEVNETS and RSNetWorxt Setup In this Appendix Setup T1K DEVNETS with RSNetWorxt...