STRIDE
®
SiteLink Series Industrial VPN Routers User Manual
1st Edition
D-7
Appendix D: Data Logging Address Notation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Do-more PLCs
Reading Coils (Function Code 1)
Function Code SiteLink Modbus Address
Data Type
Do-more! Address
1
0
BOOL
MC1
1
1
MC2
1
65534
MC65535
Reading Input Bits (Function Code 2)
Function Code SiteLink Modbus Address
Data Type
Do-more! Address
2
0
BOOL
MI1
2
1
MI2
2
65534
MI65535
Reading Input Registers (Function Code 4)
Function Code SiteLink Modbus Address
Data Type
Do-more! Address**
4
0
INT16, UINT16 or
BOOL*
MIR1
4
1
MIR2
4
65534
MIR65535
4
0
INT32 or UINT32
-
4
1/2
MIRD
4
65533/65534
MIR6553D
4
0
FLOAT32
-
4
1
MIRRD
4
65533/65534
MIR6553RD
* BOOL: When using BOOL with Input and Holding Registers, a zero value in the register indicates False in the data logger.
Any non-zero value indicates True in the data logger.
** Double integers (32 bit) can only be used on even number addresses in Do-more! (MIR2, MIR4, etc…).