background image

DPM3 User Manual, 1st Edition

User Manual - DPM3 Series Panel Meters

9

This instrument conforms with the following community directives: EMC 2004/108/CE and 

LVD 2006/95/CE.
Refer to the instructions in this manual to preserve safety protections.

WARNING: If this instrument is not installed and used in accordance with these 

instructions, the protection provided against hazards may be impaired.

To meet the requirements of EN 61010-1 standard, where the unit is permanently connected 

to main supply, it is obligatory to install a circuit breaking device easily reach by the operator 

and clearly marked as the disconnecting device.
To guarantee electromagnetic compatibility, the following guidelines should be kept in mind:

•  Power supply wires should be separately routed from signal wires and never run in the same conduit.
• Use shielded cable for signal wiring.
• Cables section should be 

0.25 mm².

Before connecting signal wires, signal type and input range should be verified to be within the 

right limits. Do not connect simultaneously more than one input signal to the meter.

Wiring Examples

Process Input Signal Wiring Diagrams (mA) 

CONNECTION WITH EXTERNAL EXCITATION

4 wire Connection 

3 wire Connection 

2 wire Connection 

(only 4-20mA)

TRANSDUCER

TRANSDUCER

TRANSDUCER

TRANSDUCER

TRANSDUCER

TRANSDUCER

4 wire Connection 

3 wire Connection 

2 wire Connection

(only 4-20mA)

0-20 mA

4-20 mA

0-20 mA

4-20 mA

0-20 mA

4-20 mA

0-20 mA

4-20 mA

4-20 mA

4-20 mA

EXTERNAL

EXCITATION

EXTERNAL

EXCITATION

EXTERNAL

EXCITATION

EXCITATION SUPPLIED BY DPM3

If the excitation supplied by the DPM3 to the transducer has to be

10V connect to the +EXC wire to PIN3 instead of PIN2 

CN2

CN2

CN2

CN2

CN2

CN2

(24V)

(24V)

(24V)

Summary of Contents for ProSense DPM3 Series

Page 1: ...input signals Models User Manual DPM3 AT H DPM3 AT L DPM3 AT 2R H DPM3 AT 2R L DPM3 AT 4R H DPM3 AT 4R L DPM3 AT A H DPM3 AT A L DPM3 AT A2R H DPM3 AT A2R L Scan or click the QR code for a series of...

Page 2: ...inals 8 Wiring Examples 9 Process Input Signal Wiring Diagrams mA 9 Process Input Signal Wiring Diagram V 10 Load Cell Input Signal Wiring Diagram 10 Pt100 Sensor Input Wiring Diagram 10 Thermocouple...

Page 3: ...n 22 Logic functions 23 Logic functions menu 24 Table of programmable functions 24 Configuration Lock Out 25 Lock out menu diagram 26 Output Options 28 Relay Configuration 28 Description of Operation...

Page 4: ...ste of electrical and electronic equipment from products put on the market after August 13 2005 the user can give it back without any cost to the place where it was acquired to proceed to its controll...

Page 5: ...best in the industry We rely on your feedback to let us know if we are reaching our goal If you cannot find the solution to your particular application or if for any reason you need technical assistan...

Page 6: ...sor excitation The 1 8 DIN housing is easy to install in a panel and the meter face has an IP65 rating Configuration parameters can be totally or selectively locked out to prevent unauthorized or acci...

Page 7: ...nd the front bezel While holding the unit in place put the fixing clips on both sides of the case and slide them through the guide tracks until they reach the panel at the rear side Press slightly to...

Page 8: ...5mm 28 to 12 AWG 0 08 to 0 5mm 28 to 20 AWG 0 08 to 0 5mm 28 to 20 AWG 0 08 to 2 5mm 28 to 12 AWG 0 08 to 2 5mm 28 to 12 AWG Strip length 8 to 9mm 5 to 6mm 5 to 6mm 8 to 9mm 8 to 9mm Manufacturer Wago...

Page 9: ...d be separately routed from signal wires and never run in the same conduit Use shielded cable for signal wiring Cables section should be 0 25 mm Before connecting signal wires signal type and input ra...

Page 10: ...wire Connection 3 wire Connection TRANSDUCER 0 10 V POTENTIOMETER CI METRO EXC 10V OUT OUT 24V 24V If the excitation supplied by the DPM3 to the transducer has to be 10V connect to the EXC wire to PIN...

Page 11: ...DPM3 User Manual 1st Edition User Manual DPM3 Series Panel Meters 11 Thermocouple J K T N Sensor Input Wiring Diagram Thermocouple type J K T N 7 8 CN2 Terminals...

Page 12: ...program 9 Free space for units label 10 LED Output 4 Activation Output 4 Programming output 4 11 LED Output 3 Activation Output 3 Programming output 3 12 LED Output 2 Activaton Output 2 Programming ou...

Page 13: ...t step of the program Programming numerical values When the parameter is a numerical value the display will show the first of the digit to be programmed blinking Digit selecting Press repeatedly the S...

Page 14: ...of the different types of input process load cell Pt100 RTD and thermocouple ENTER Vertical displacement UP Changes active digit SHIFT Horizontal displacement Programming Keys Bottom view 1 Process In...

Page 15: ...s selection of the input range which may be selected high enough for the maximum input signal to avoid overloads There are three ranges 15 mV 30 mV and 150 mV Example If a weighing process gives 12 mV...

Page 16: ...ypes of thermocouples temperature units Celsius or Fahrenheit resolution degree or tenth of degrees and a display offset Offset value is programmed for a known difference between the temperature under...

Page 17: ...automatically scaled to a fixed range based on the temperature sensor Scaling consists of assigning a display value to each input signal value In linear processes it is achieved by programming two co...

Page 18: ...e repeated for different inputs Below the first point programmed the relationship established between the two first points of the scale is followed Above the last point programmed the relationship est...

Page 19: ...programming routine The rest of the points up to 11 that have not been programmed are omitted from the display calculation Input Points 19999 to 99999 Display Points 19999 to 39999 Display decimal poi...

Page 20: ...gnal is lower than the minimum display will show No Without indication Additional Functions Several functions can be controlled via Key Pad that will produce different actions depending on the instrum...

Page 21: ...ly enter and store a new tare value of zero The TARE Led will turn off and the displayed value will be the measured value without the tare value applied tare 3 To configure the meter for Tare 3 mode s...

Page 22: ...e security code If the code that has been introduced is wrong the meter will go back to RUN mode if it is correct it will allow the access to the security menu See section detailing Configuration Lock...

Page 23: ...etween 0 and 15 corresponding to one of the functions listed in the following table Factory configuration As shipped from the factory the CN3 connector allows remote control of the TARE RESET TARE fun...

Page 24: ...to the tare memory and sets the display to zero Falling edge 2 TARE RESET Adds the tare memory to the display value and clears the tare memory Falling edge 3 LIST RESET Performs a reset of the peak M...

Page 25: ...The access to the programming routines to read data is allowed even if all parameters are locked out totLC 1 but it won t be possible to enter or modify data In this case when entering in the program...

Page 26: ...t on your memory If an incorrect code is entered the meter will return automatically to the run mode Total lockout programming is achieved by changing the totLC variable to 1 changing it to 0 will lea...

Page 27: ...1st Edition User Manual DPM3 Series Panel Meters 27 0 allows its programming 1 locks the access to programming Only appear if the corresponding options are present in the meter 0 0 1 Previous Page 1...

Page 28: ...value exceeds the setpoint level and in LO mode the output activates when the display value falls below the setpoint c RELAYS CONTACT DEFAULT STATE NO NC Defines relays contact status by default NO no...

Page 29: ...ation menu diagram The complete programming of one of the setpoints is showed here it is valid for the rest of the setpoints Only available if the DPM3 model has 4 relays or if the logic function 10 h...

Page 30: ...output 4 20 mA The output is optoisolated with respect to the signal input and the power supply The meter provides a two terminal connector and that drives out a signal variation from 4mA to 20mA pro...

Page 31: ...igured to be fixed at a high level Hi or a low level Lo Analog output menu diagram Display value for output 20 mA Display value for output 4 mA 4 188 88 outLo Overrange indication by high level Hi mA...

Page 32: ...0 2 rdg 1 F 0 1 F 0 2 rdg 2 F 1 F Pt100 sensor excitation 1mA DC Max lead resistance 40 cable balanced Thermocouple J K T N Fixed display range resolution 150 0 C to 1100 0 C 0 1 C 150 C to 1100 C 1...

Page 33: ...t resistance 100m at 6VDC at 1A Operate time 10ms Nominal contact rating 5A at 250VAC 30 VDC Maximum switching current resistive load 5A Maximum switching power 1250VA 150W Maximum switching voltage 2...

Page 34: ...DPM3 User Manual 1st Edition User Manual DPM3 Series Panel Meters 34 Notes...

Reviews: