DPM3 User Manual, 1st Edition
User Manual - DPM3 Series Panel Meters
17
Display Configuration
3s?
-
-
-
-
-
-
±
.
±
±
±
±
.
HI
Lo
±
.
±
±
±
±
.
2
3s?
-
-
Decimal point selection
Lo
Note: the color selection of the alarms is
made in the setpoints menu
(Red)
(Green)
(Amber)
(Red)
(Green)
(Amber)
-
-
Lo
-
-
Lo
-
-
To configure additional
points of a nonlinear process
press ENTER for more
than 3s
ENTER:
Vertical displacement.
UP:
Changes active digit.
SHIFT:
Horizontal displacement.
Decimal point selection
Programming Key Pad
Scaling
It is only necessary to scale the meter when it has been configured for a process or a load cell
input signal. When configured for temperature sensor input the meter is automatically scaled
to a fixed range based on the temperature sensor. Scaling consists of assigning a display value to
each input signal value.
In linear processes
it is achieved by programming two coordinates (InP1, DSP1) and (InP2,
dSP2), between which is established a linear relation where each input signal value corresponds
to a display value. The relationship can be direct or reversed. In order to obtain more accuracy,
points 1 and 2 should be located approximately at both extremes of the process.
display2
display1
input1
Input2
Direct scale
input2
input1
display1
display2
Reversed scale
In nonlinear processes it is possible to program up to 11 input to display points. Each two
points are connected by a straight line and the whole is a curve that represents the relationship
between the input value and the display value.