IRD (D2) Led Is Flashing
MRT (Maximum Run Timer) has expired. Gate was unable to reach the closed limit switch. Check that
fast run timer is set to run as long as possible. (SW1 #’s 1-5 should all be on).
Fuse(s) Are Blown
F3 (15 AMP AC) AND/OR F4 (15 AMP DC) Check for shorts in wiring. If F3 AC fuse is blown, then
batteries may also be dead. If you continue to blow fuses and no apparent shortages are visible, you
most likely have a blown control board and it will need to be replaced.
Gate Closes Then Reverses
See IRD adjustments, also check for obstacles in gate travel, such as trees, sticks, etc. Check batteries
for voltage, if batteries are weak, it can cause the gate to not reach the close limit and re-open.
Charge Voltages
Charge voltage to batteries too low, adjust at R63. With batteries disconnected, set to 27.5.
Motor Doesn’t Stop
If gate closes and motor continues to run the limit switch may need adjustment or replacement.
IRD Obstruction Signal to Other Gate Note Working Correctly
Remove connector at J3, obstruct gate, LED D13 should go off for a few seconds. This indicates signal
was transmitted. Be sure gates have a common ground.
Manual Operation
The VP gate is easily operated manually in the event of total power or component failure.
1. Turn main power switches off (both A/C & D/C).
2. Release the belt tension lever located under the gear motor to remove the belt tension.
3. Position yourself in front of operator and lift up on Linkage Arm at the pivot point 1”-2”.
4. Walk out to end of gate and lift gate to the open position.
5. Place the T/M pin through the bracket holes to prevent the gate from lowering.
6. Secure the belt tension lever in the locked position to re-apply tension to the belts.
NOTE:
It only takes 16 - 30 lb. of force to open gate. If more is required, contact your dealer or
AutoGate.
Summary of Contents for VPG-24 (LM)
Page 27: ...1 800 944 4283 AutoGate Technical Support JULY 2016 27...
Page 31: ...1 800 944 4283 AutoGate Technical Support JULY 2016 31...
Page 32: ...1 800 944 4283 AutoGate Technical Support JULY 2016 32...
Page 33: ...1 800 944 4283 AutoGate Technical Support JULY 2016 33...
Page 34: ...1 800 944 4283 AutoGate Technical Support JULY 2016 34...
Page 35: ...1 800 944 4283 AutoGate Technical Support JULY 2016 35...
Page 36: ...1 800 944 4283 AutoGate Technical Support JULY 2016 36...
Page 37: ...1 800 944 4283 AutoGate Technical Support JULY 2016 37...
Page 38: ...1 800 944 4283 AutoGate Technical Support JULY 2016 38...
Page 39: ...1 800 944 4283 AutoGate Technical Support JULY 2016 39...
Page 40: ...1 800 944 4283 AutoGate Technical Support JULY 2016 40...
Page 41: ...1 800 944 4283 AutoGate Technical Support JULY 2016 41...
Page 42: ...1 800 944 4283 AutoGate Technical Support JULY 2016 42...