ZONEMIX
INSTALLATION AND OPERATION MANUAL
15
DATE/TIME
The Date and Time can be set from the front panel system setup menu or
from the PC control software. The ZONEMIX has an integrated real time
clock (RTC) to maintain the clock however it will drift over time.
CLOCK ACCURACY
If you are using the scheduler, it is HIGHLY recommended to attach the
ZONEMIX to a network via the Ethernet connector and to set the Network
Time Protocol (NTP) settings. The allows the ZONEMIX to retrieve date and
time information from the network to ensure they are always accurate.
• Select the Date/Time control
• Select your time zone
• Use the default NTP address or enter your network NTP server address
• Finally, if required, enter any daylight savings dates for your region
GENERAL PURPOSE INPUTS AND OUTPUTS
The ZONEMIX4 and ZONEMIX8 have 4 inputs and outputs and 8 inputs and outputs respectively.
Use the PC control software to configure the I/O,
Use the dropdown menus to select the desired function for the input or output.
INPUTS
• Enable Master Override
• Mute Zone/s Master
• Recall a preset
• Trigger a message from the SD card
OUTPUTS
• Scheduler controlled
• Paging Active
• Wall Panel Control
ELECTRICAL SPECIFICATIONS:
Each INPUT detects the following levels
• Low input must be less than 0.5V
• High must be greater than 3V but less than 12V
• Input triggers must be stable for longer than 150ms.
Each OUTPUT is configured as follows,
• Open collector
• Can be connected to up to 50V systems
• Maximum 300mA sinked current
The 24V output can draw a maximum of 100mA.
PC CONTROL SOFTWARE CONT.
DAYLIGHT SAVING
Daylight savings dates can be entered if required in your territory. The
time change will be actioned at 3am on the date specified.