5
Technical data
PANAMA 500A
080480
PANAMA 1000A
080484
Mini
Quiet
Maxi
Mini
Quiet
Maxi
50°C / -
Power
(W)
430
780
1070
565
1500
2210
Primary water flow
(L/H)
38
99
136
58
180
264
Pressure losses
(Kpa)
1.9
3.6
5
2.2
9.0
13.3
45°C / 40°C
Power
(W)
384
700
954
487
1300
1905
Primary water flow
(L/H)
67
121
166
85
226
331
Pressure losses
(Kpa)
3.1
5.4
7.4
3.7
16.7
24.4
35°C / 30°C
Power
(W)
204
370
507
262
700
1025
Primary water flow
(L/H)
35
64
88
46
121
178
Pressure losses
(Kpa)
1.8
3.0
4.1
1.4
7.1
10.4
7°C / 12°C
Power
(W)
220
480
780
335
703
1520
Sensible power
(W)
200
400
640
271
550
1220
Primary water flow
(L/H)
38
83
136
58
122
264
Pressure losses
(Kpa)
2
3.3
6
2.1
5.6
17.2
Electric
Fan consumption (heating mode)
(W)
3.2
5.4
10.2
4.2
10
17.2
Electric backup (Elec.front film)
(W)
190
290
Acoustics
Power
(dBA)
29
37
42
29
37
43
Pressure (at 1.5 meter)
(dBA)
18
23
29
18.5
23
31
Aeraulics
Air flow
(m3/H)
55
103
150
85
193
290
Installation
Dimension (H x W x D)
(mm)
678 x 635 x 178
678 x 920 x 178
Weight
(Kg)
13.5
18.5
OPERATIONAL LIMITATION
-
Incoming water m
inimum temperature : 5°C
-
Incoming water maximum temperature: 65°C
-
Air intake minimum temperature: 5°C
-
Air intake maximum temperature: 40°C
-
Incoming water maximum pressure: 0.8 MPa
-
Incoming water minimum pressure: 0.12 MPa
-
Range of external static pressures: 980-1030 hPa
-
Protection rating of the device: IP24
DIMENSIONS OF THE DEVICE