PE4104G User Manual
22
Heading
Meaning
Outlet
Shows the port number of the listed outlet.
Outlet Name
Each outlet can be given a distinctive name. The maximum
number of characters is 48.
Confirmation
Required
If this option is enabled (there is a check in the checkbox), a dialog
box comes up asking you to confirm a power operation before it is
performed. If it is disabled (there is no check in the checkbox), the
operation is performed without confirmation.
Delay Time (sec)
Power ON
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 20), before it turns on the power
to the outlet. You must check the
Enable Power On Time Schedule
Setting
box for this setting to take effect. See
Note:
The default delay time is 1 seconds; the maximum is 999
seconds. When a series of outlets are scheduled to be powered
up, they turn on in sequence with a default delay of 10
milliseconds between each outlet.
Delay Time (sec)
Power OFF
Sets the amount of time the eco PDU waits after the Power Button
is clicked (see
, page 20), before it turns off the power
to the outlet.
For the
System after AC Back
option (see below), after the delay
time expires, the eco PDU waits another fifteen seconds, then
shuts the computer down.
The default delay time is 5 seconds. The maximum delay time is
999 seconds.