29
8___PROGRAMMING MEMO
VARIABLES DEFAULT VALUES
SETTINGS
COMMENTS
PH SETTINGS
SET
7.20 pH
pH SET POINT pH
ALL
6.50 pH
pH minimum alarm
ALH
7.90 pH
PH maximum alarm
REL
ACID
Type of control
PRS
NO
Status of the pH relay
DEL
0 Seconds
Delay time, pH metering
SPM
20 Strokes/min.
Strokes/minute, Output
Freq.
BP
0.50 pH
Proportional band (pH)
REG
ONOF Control mode
OUT
MIS
MA output working mode
HIS
0.00 pH
Hysteresis (pH)
RMA
4-20 mA
MA output dynamics
MMA
0.1 mA
Offset Output mA
PHS
0 pH
Initial value for reg. mA
PHE
14.00 pH
End value for per reg. mA
Ton
0 Seconds
ON time (Reg. Puls.)
Tof
0 Seconds
OFF time (Reg. Puls.)
BND
0.00 pH
Safety band
PER
500 Seconds
Period (Reg. Prop.)
MON
0 Seconds
Minimum ON time
DB
0 % of BP
dead band (reversed
hysteresis)
CHLORINE SETTINGS
SET
0.60 ppm
Chlorine SET POINT
ALL
0.30 ppm
Chlorine minimum alarm
ALH
1.50 ppm
Chlorine maximum alarm
REL
LO
Type of control
PRS
NO
Status of chlorine relay
DEL
0 Seconds
Chlorine-metering delay
time
SPM
20 Strokes/min.
Strokes/minute, Output
Freq.
BP
0,50 pH
Proportional band
REG
ONOF Control mode
OUT
MIS
Working mode Output mA
HIS
0.00 ppm
Hysteresis
RMA
4-20 mA
MA output dynamics
MMA
0,1 mA
Offset Output mA
CLS
0 ppm
Initial value for reg. mA
CLE
5.00 ppm
End value for per reg. mA
Ton
0 Seconds
ON time (Reg. Puls.)
Tof
0 Seconds
OFF time (Reg. Puls.)
BND
0.00 ppm
Safety band
PER
500 Seconds
Period (Reg. Prop.)
MON
0 Seconds
Minimum ON time
DB
0 % of BP
dead band (reversed
hysteresis)
CTP
0 %/°C
Coefficient for offsetting the
measured value in relation to the
temperature expressed in %/°C.
CPH
OFF
Enables correction of the chlorine
measurement in relation to the pH
ENABLING
EN
SC
Enables the Cal and Set
keys
ID
1
Indicates the ID of the multi-point
serial network
BR
2400
Baud rate of RS485 serial link