![Astralpool PC95 Instruction Manual Download Page 52](http://html1.mh-extra.com/html/astralpool/pc95/pc95_instruction-manual_2990608052.webp)
23
7.3___PROP
Enter the programming menu (
See Page 16
) and go to the
PRG2
function.
VARIABLES
PERMISSIBLE LIMITS
DEFAULT VALUES
COMMENTS
PH SETTINGS
SET
7,20 pH
SET POINT pH
ALL
6,50 pH
PH minimum alarm
ALH
7,90 pH
PH maximum alarm
REL
ACID
Type of control
PRS
NO
Status of the pH relay
DEL
0 Seconds
Delay time, pH metering
SPM
20 Strokes/min.
Strokes/minute, Output
Freq.
BP
0,50 pH
Proportional band
REG
PROP
Control mode
OUT
MIS
Working mode Output mA
PER
500 Seconds
Period (Reg. Prop.)
MON
0 Seconds
Minimum ON time
DB
0 % of BP
dead band (reversed
hysteresis)
RMA
4-20 mA
MA output dynamics
PHS
0 pH
Initial value for mA control
PHE
14,00 pH
End value for per mA
control
CHLORINE SETTINGS
SET
0.60 ppm
SET POINT Chlorine
ALL
0.30 ppm
Chlorine minimum alarm
ALH
1.50 ppm
Chlorine maximum alarm
REL
LO
Type of control
PRS
NO
Status of chlorine relay
DEL
0 Seconds
Chlorine-metering delay
time
SPM
20 Strokes/min
Strokes/minute, Output
Freq.
BP
0.50 ppm
Proportional band
REG
PROP
Control mode
OUT
MIS
Working mode Output mA
PER
500 Seconds
Period (Reg. Prop.)
MON
0 Seconds
Minimum ON time
DB
0 %di BP
dead band (reversed
hysteresis)
RMA
4-20 mA
MA output dynamics
CLS
0 ppm
Initial value for mA control
CLE
14.00 ppm
End value for per mA
control
CTP
0 %/°C
Coefficient for offsetting the
measured value in relation
to the temperature
expressed in %/°C.
CPH
OFF
Enables correction of the
chlorine measurement in
relation to the pH
ENABLING
EN
SC
Enables the Cal and Set
keys
ID
1
Indicates the ID of the multi-
point serial network
BR
2400
Baud rate of RS485 serial
link
Time-related proportional control enables any changes in the measurement to be followed up
rapidly, optimising the metering in relation to the distance from the set point.
Summary of Contents for PC95
Page 1: ...Manual de Instrucciones PC95 pH cloro temperatura Cod 136317 Manual 0000136317 Versi n r 2 0...
Page 30: ...Instruction Manual PC95 pH chlorine temperature Cod 0000136317 Manual 0000136317 Version r 2 0...
Page 59: ...Manuale Istruzioni PC95 cod 136317 pH cloro temperatura Manuale 0000136317 Versione r 2 0...