20
This is the simplest and most elementary type of control that can be implemented. The metering
device is switched on as soon as the SET POINT measurement is exceeded, and switched off
again as soon as the measurement returns to less than a given value to be set, that is defined as
HYSTERESIS.
The HYSTERESIS value makes it possible to avoid constant switching on and off of the metering
device. Limited hysteresis improves control, but to the detriment of the metering device, which
would be subject to greater wear (graphs on page 19).
7.2___PULS
Enter the programming menu (
See Page 16
) and go to the
PRG2
function.
VARIABLES DEFAULT
VALUES
COMMENTS
PH SETTINGS
SET
7,20 pH
SET POINT pH
ALL
6,50 pH
PH minimum alarm
ALH
7,90 pH
PH maximum alarm
REL
ACID
Type of control
PRS
NO
Status of the pH relay
DEL
0 Seconds
Delay time, pH metering
SPM
20 Seconds
Strokes/minute, Output
Freq.
BP
0,50 Seconds Proportional
band
REG
PULS
Control mode
OUT
MIS
Working mode Output mA
HIS(*)
0,00 pH
Hysteresis
Ton
0 Seconds
ON time (Reg. Puls.)
Tof
0 Seconds
OFF time (Reg. Puls.)
BND
0,00 pH
Safety band
RMA
4-20 mA
MA output dynamics
PHS
0 pH
Initial value for mA control
PHE
14,00 pH
End value for per mA
control
CHLORINE SETTINGS
SET
0,60 ppm
SET POINT Chlorine
ALL
0,30 ppm
Chlorine minimum alarm
ALH
1,50 ppm
Chlorine maximum alarm
REL
LO
Type of control
PRS
NO
Status of chlorine relay
DEL
0 Seconds
Chlorine-metering delay
time
SPM
20 Seconds
Strokes/minute, Output
Freq.
BP
0,50 ppm
Proportional band
REG
PULS
Control mode
OUT
MIS
Working mode Output mA
HIS
0,00 ppm
Hysteresis
Ton
0 Seconds
ON time (Reg. Puls.)
Tof
0 Seconds
OFF time (Reg. Puls.)
BND
0,00 ppm
Safety band
RMA
4-20 mA
MA output dynamics
CLS
0 ppm
Initial value for mA control
CLE
5,00 ppm
End value for per mA control
CTP
0 %/°C
Coefficient for offsetting the
measured value in relation to the
temperature expressed in %/°C.
CPH
OFF
Enables correction of the chlorine
measurement in relation to the pH
ENABLING
EN
SC
Enables the Cal and Set keys
ID
1
Indicates the ID of the multi-point
serial network
BR
2400
Baud rate of RS485 serial link
Summary of Contents for PC95