18
6.1.2___ PRG2 menu
Enter the programming menu (
See Page 16
) and go to the
PRG2
function.
The variables displayed are the following:
VARIABLES
PERMISSIBLE LIMITS
DEFAULT VALUES
COMMENTS
PH SETTINGS
SET
0 to 14.00
7.20 pH
SET POINT pH
ALL
0 to SET
6.50 pH
pH minimum alarm
ALH
SET to 14.00
7.90 pH
pH maximum alarm
REL
ACID/ALCA
ACID
Type of control
PRS
NO / NC
NO
Status of the pH relay
DEL
0 to 255
0 Seconds
Delay time, pH metering
SPM
20 to 150
20 strokes/min
Strokes/minute, Output
Freq.
BP
0.50 to 2.80
0,50 pH
Proportional band
REG
ONOF/PULS/PROP ONOF
Control mode
OUT
MIS/REG
MIS
Working mode Output mA
HIS
0.02 to 1.40
0.00 pH
Hysteresis
RMA
0-20/ 4-20
4-20 mA
MA output dynamics
MMA
0.1 to 5.00
0.1 mA
Offset Output mA
PHS
0 to 10.00
0 pH
Initial value for reg. mA
PHE
PHS to 14.00
14.00 pH
End value for per reg. mA
Ton
0 to 999 seconds
0 Seconds
ON time (pulsed control)
Tof
0 to 999 seconds
0 Seconds
OFF time (pulsed control)
BND
0.00 to 2.00 pH
0.00 pH
Safety range
PER
0 to 999 seconds
500 Seconds
Period (pulsed control)
MON
0 to 255 seconds
0 Seconds
Minimum ON time
DB
0 to 10% BP
0 % of BP
dead band (reversed
hysteresis)
CHLORINE SETTINGS
SET
0 to 5.00
0,60 ppm
Chlorine SET POINT
ALL
0 to SET
0,30 ppm
Chlorine minimum alarm
ALH
SET to 5.00
1,50 ppm
Chlorine maximum alarm
REL
LO
LO
Type of control
PRS
NO / NC
NO
Status of chlorine relay
DEL
0 to 255
0 Seconds
Delay time for chlorine
metering
SPM
20 to 150
20 Strokes/min.
Strokes/minute, Output
Freq.
BP
0.50 to 2.80
0,50 ppm
Proportional band
REG
ONOF/PULS/PROP ONOF
Control mode
OUT
MIS/REG
MIS
Working mode Output mA
HIS(*)
0.02 to 0.50
0.00 ppm
Hysteresis
RMA
0-20/4.20
4-20 mA
Output dynamics in mA
MMA
0.1 to 5.00
0.1 mA
Output dynamics mA
CLS
0 to 4.00
0 ppm
Initial value for mA control
CLE
PHS to 5.00
5.00 ppm
End value for per mA
control
Ton
0 to 999 seconds
0 Seconds
ON time (pulsed control)
Tof
0 to 999 seconds
0 Seconds
OFF time (pulsed control)
BND
0.00 to 2.00
0.00 ppm
Safety band
PER
0 to 999 seconds
500 seconds
Period (Reg. Prop.)
MON
0 to 255 seconds
0 seconds
Minimum ON time
DB
0 to 10% BP
0 % of BP
dead band (reversed hysteresis)
CTP
0 to 10
0 %/°C
Coefficient for offsetting the the
measured value in relation to the
temperature expressed in %/°C.
CPH
ON / OFF
OFF
Enabling of correction of the
chlorine measurement in relation to
the pH.
ENABLING
EN
S-/-C/SC/-- SC
Enables the Cal and Set keys
ID
1 to 30
1
Indicates the ID of the multi-point
.serial network
BR
1200 to 9600
2400
Baud rate of RS485 serial link