3
1___TECHNICAL SPECIFICATIONS
SIZE:
240
mm
–
245
mm
–
140
mm
CLASS OF PROTECTION:
IP65 PROTECTING THE BNC OF THE PH electrode
CROSS-SECTION OF TERMINALS:
4mm
2
, or diameter 2.4 mm
POWER SUPPLY REQUIREMENTS:
standard 230V
r
10% 50-60 Hz, on request 115V
ABSORPTION:
15W
MAX. CAPACITY ON RELAYS:
3A 250VAC (with resistive load)
WORKING TEMPERATURE
0 to 50 ° C
1.1
STORAGE TEMPERATURE
-10 to 70 °C
SCALE OF MEASUREMENT OF THE pH:
0…14.00 pH
INPUT IMPEDANCE:
> 10
13
ohm
TEMPERATURE OFFSETTING:
MANUAL/AUTOMATIC 0 to 125 °C
CONTROL OVER SET POINT:
ON/OFF
BREAK/WORK
CURRENT, PROPORTIONAL
Remote repetition of the measurement:
0/4 to 20 mA galvanically separated
Can be fully configured for re-transmission of measurement or control
Resolution
255
points
Maximum load 1 K Ohm
SCALE OF MEASUREMENT OF Cl:
0 to 5.00 ppm or mg/l
TEMPERATURE OFFSETTING:
Excludable
MANUAL/AUTOMATIC 0 to 125 °C
PH
OFFSETTING:
Excludable
Range
of
compensation
6
to
8.35
pH
CONTROL OVER SET POINT:
ON/OFF
BREAK/WORK
CURRENT, PROPORTIONAL
RE-TRANSMITTED OUTPUT :
0/4 to 20 mA galvanically separated
Can be fully configured for re-transmission of measurement or control
Resolution
255
points
Maximum load 1 K Ohm
N.B.
In swimming-pool water treated with DICHLOR or TRICHLOR-isocyanate it is
important to provide a good change of the water so that the residual isocyanate acid will
not exceed 50 ppm in order to ensure correct chlorine measurement.