GENERAL DESCRIPTION OF THE SIGNALLING LAMPS
PH measurement display
Chlorine measurement display
Two-coloured LED. This indicates the status of the pH pump
OFF
The pH pump is switched off.
GREEN
The set point is active however the pump is temporarily
switched off
RED
The set point is active and the pump is switched on.
FLASHING RED
During programming, it indicates that the parameter being
displayed refers to control of the pH set point.
Two-coloured LED. This indicates the status of the chlorine pump
OFF
The chlorine pump is switched off.
GREEN
The set point is active however the pump is temporarily
switched off
RED
The set point is active and the pump is on.
FLASHING RED
In the programming phase, this indicates that the
parameter being displayed refers to control of the Chlorine
set-point.
Red LED. This indicates an alarm status.
FLASHING RED
An alarm status has occurred and the alarm relay is active.
To reset the alarm press the ACK key.
RED
An alarm has been acknowledged by pressing the ACK
key, however the cause leading to the alarm is still
present. The alarm LED will extinguish once the cause of
the alarm has been eliminated.
Red LED. This indicates a status of total stoppage of the functions of the instrument.
RED
When it is illuminated, it signals a temporary block of operation of the pumps. The current outputs
remain locked on the last value that was re-transmitted.
CALIBRATION FUNCTIONS
6
7 pH
The instrument prompts you to dip the electrode into a
standard solution having a pH of 7. It is therefore ready to
carry out calibration of the offset on the pH electrode
4 pH
The instrument prompts you to dip the electrode into a
standard solution having a pH of 4. It is therefore ready to
carry out calibration of the gain on the pH electrode
Cl
2
The instrument is ready to carry out self-calibration of the
chlorine measurement. It is waiting for the chlorine value
measured by means of the DPD method to be entered.
Summary of Contents for PC95
Page 1: ...Manual de Instrucciones PC95 pH cloro temperatura Cod 136317 Manual 0000136317 Versi n r 2 0...
Page 30: ...Instruction Manual PC95 pH chlorine temperature Cod 0000136317 Manual 0000136317 Version r 2 0...
Page 59: ...Manuale Istruzioni PC95 cod 136317 pH cloro temperatura Manuale 0000136317 Versione r 2 0...