D6021/D6031 Double Unit Series
(Push Side) Power Operator
Double Door Electric Latch Retraction Exit Device Wiring
Double Door Electric Latch Retraction Exit Device Wiring for Smoke Ventilation -
Blow Open Function
Change Factory Pre-Wiring to Illustration Below (move GND to COM)
NOTE: This application must
be approved by local (AHJ)
authority having jurisdiction.
•
For Master/Follow or Master-
Coord/Follow only (Sync
Cable must be used to
connect inverters.)Doors are
normally closed and latched.
• Fire Alarm activation will
retract exit device latch bolt
and door operator will open
door.
• Door will remain open until
the Fire Alarm System has
been reset.
• Door Operator’s main power
input must be wired into
building’s back-up power
system.
• Exit device allows egress at
all times. Exit device allows
egress during power failure.
Change Factory Pre-Wiring to Illustration Below (move GND to COM)
•
For Master/Follow or
Master-Coord/Follow only
(Sync Cable must be used
to connect inverters.)
• Doors are normally closed
and latched.
• Activating switch will
retract exit device latch
bolt and operator will
open door.
• Door will close after hold
open time delay has
elapsed.
• Exit device allows egress
at all times. Exit device
allows egress during
power failure.
• Contact Tech Support
for other devices
or manufacturer’s
instructions.