Copyright © 2019, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.
80-9360-1030-020 Rev 6 11/20
14
D6021/D6031 Double Unit Series
(Push Side) Power Operator
You’ve now installed the
D6021 or D6031 PUSH SIDE Low Energy Operator.
Continue with Electrical Instructions to customize the installation.
Sync Operators
1. Determine which door will be Master.
2. Run Sync Cable between operators. (Figure 29)
•
Attach end of Sync Cable marked “M” to 4-pin connector
on top of inverter board on unit selected as Master Door.
•
Attach other end of Sync Cable marked “F” to 4-pin
connector on top of inverter board selected as Follower
Door.
NOTE: Connectors are keyed and only attach one way.
3.
To set up inverter for Master - Follower functionality:
Master Unit:
• go to Page 2 on inverter screen
• scroll down to Single
• increase to Dbl:Master or
*Dbl:MasterCoord
Follower Unit:
• go to Page 2 on inverter screen
• scroll down to Single
• increase to Dbl:Follower
*NOTE: Dbl:MasterCoord to be used when astragal or
similar is attached to Master door or as a replacement
for a mechanical door coordinator. Once set, Master
Figure 29
Union Assembly Switches
door will open slightly before Follower door during
opening cycle. Upon closing, if Master door reaches
a set door opening position (MasterStopOffset) and
Follower door has not reached full closed position,
Master door will stop and wait for Follower door to
reach fully closed and then close. The point at which
Master door stops (MasterStopOffset) is adjustable.
*NOTE: If Dbl:MasterCoord is used and Follower door
is opened manually, Master door will automatically
open to MasterStopOffset position until Follower
door has reached fully closed position and then close.
4. Make necessary adjustments to Master Door inverter
only, add activation to Master Door inverter only, and
add required accessories to each door.
NOTE: Settings will automatically transfer over to
Follower Door inverter.
5. Place both selector mode switches of union assembly
in ‘ON’ position for activation by push plate, RF button,
or other activation devices. Place switches in ‘H/O’ for
continuous hold open. (Figure 29)
6. Secure union assembly door with #4 Phillips screw.