ADR111A /
ADR211A
This setting is used to set parity. It is important that both relay and master station are set with the same parity
setting.
17.
Baud Rate
9600
2400/ 4800/ 9600/ 14400/ 19200
This setting is used to set Baud rate. It is important that both relay and master station are set with the same
Baud rate setting.
18.
Hrm. Rst.
10
00 – 80% in step of 5%
This setting is specify the 2nd Harm Threshold value, if the level of 2nd harmonic exceeds the setting, the
over current protection will be blocked.
6.2
Date and Time setting
Sr. No
Parameter
Defaults setting
Settings / Ranges
1.
SET Hours
00
00 – 23 Hrs in step 1.
Hour
setting
needed when relay is not connected to SCADA system
2.
SET Minutes
00
00 – 59 Mins in step 1.
Minutes
setting
needed when relay is not connected to SCADA system
3.
SET Seconds
00
00 – 59 Sec. in step 1.
Seconds
setting
needed when relay is not connected to SCADA system
4.
SET Date
01
01 – 31 Days in step of 1.
Date
needed when relay is not connected to SCADA system
5.
SET Month
01
01 – 12 Months in step of 1.
Month
needed when relay is not connected to SCADA system
6.
SET Year
01
00 – 99 Years in step of 1.
Year
needed when relay is not connected to SCADA system
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......