Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/I&S
Rev No.
: 04
Page No. : 24 of 127
ADR111A /
ADR211A
VII.
Conducted
Disturbance
Induced By Radio
Frequency Field
IEC60255-22-6,
IEC60255-26
(ed3) : 2013
Voltage Level
Frequency Range
Modulation
EUT Condition
Spot Frequency
10 V
0.15 – 80 MHz
80% AM @ 1 KHz
Energized
27, 68 MHz
VIII.
Power Supply
Immunity Test
IEC60255-11
IEC61000-4-11
IEC61000- 4-29
IEC60255 – 26
(Ed3) : 2013
: AC voltage dip:
40%:
70%:
80%:
200 ms
500ms
5s
AC Interruption:
10ms. 20ms, 50ms, 100ms, 200ms, 0.5s and 5s
DC Voltage dip:
40% :
70% :
200ms
500ms
DC Interruption:
10ms, 20ms, 30ms, 50ms, 100ms, 200ms, 0.5s,
1s and 5s
IX.
Conducted &
Radiated
frequency
Emission Test
IEC60255-25,
IEC60255-26
(ed3) : 2013
: Conducted
Frequency Range
0.15 – 0.5 MHz
0.5 – 30 MHz
EUT Condition
Limit
79 dB/µV (Quasi peak)
66 dB/µV (Average)
73 dB/µV (Quasi peak)
60 dB/µV (Average)
Energized
: Radiated
Frequency Range
30 MHz – 230 MHz
230 MHz – 1000 MHz
EUT Condition
Limits
50 dB (µV/m)
57 dB (µV/m)
Energized
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......