Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/I&S
Rev No.
: 04
Page No. : 25 of 127
ADR111A /
ADR211A
Insulation Tests:
I.
Dielectric Test
IEC60255-27
: At 2kV 50Hz
a) Between all terminals connected together and
case earth for 1 minute
b) Between independent circuits with case earth
for 1 minute.
II.
Impulse Voltage
Test
IEC60255-27
Test Voltage
Energy
No. of impulses
Polarity
EUT Condition
5kv, 1.2/50 µSec
0.5 J
3 on each
+ve and –ve
Non Energized
III.
Insulation
Resistance
IEC60255-27
:
≥
100M
Ω
@ 500V DC
Environmental tests:
I.
Cold test
: IEC-60068-2-1
II.
Dry heat test
: IEC-60068-2-2
III.
Damp heat test, steady state
: IEC-60068-2-78
IV.
Change of Temperature
: IEC-60068-2-14
V.
Damp heat test, cyclic
: IEC-60068-2-30
VI.
Enclosure Protection Test
IP52 (with optional IP cover)
IP31 (without optional IP cover)
: IEC 60529
CE compliance
I.
Immunity
: IEC-60255-26
II.
Emissive Test
: IEC- 60255-26
III.
Low voltage directive
: EN-50178
Mechanical tests
I.
Vibration
Endurance Test
: IEC 60255-21-1 class 2
: Frequency Range = 10Hz – 250Hz, acceleration. = 2gn
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
II.
Vibration
Response Test
: IEC 60255-21-1 class 2
: Frequency Range = 10Hz – 150Hz , acceleration. = 1gn
: Sweep rate 1 octave/min; Displacement =0.075mm, in 3
orthogonal axis.
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......