Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/SGI
Rev No. : 04
Page No. : 5 of 127
ADR111A /
ADR211A
INSTALLING, COMMISSIONING AND SERVICING
Equipment connections
Personnel undertaking installation, commissioning or servicing work for this equipment to be
aware of the correct working procedures to ensure safety. The equipment documentation
should be consulted before installing, commissioning or servicing the equipment. Terminals
exposed during installation, commissioning and maintenance may present a hazardous
voltage unless the equipment is electrically isolated. Any disassembly of the equipment may
expose parts at hazardous voltage; also electronic parts may be damaged if suitable
electrostatic voltage discharge (ESD) precautions are not taken.
If there is unlocked access to the rear of the equipment, care should be taken by all
personnel to avoid electric shock or energy hazards. Voltage and current connections should
be made using insulated crimp terminations to ensure that terminal block insulation
requirements are maintained for safety.
To ensure that wires are correctly terminated. The correct crimp terminals, tools of the wire
size should be used. The equipment must be connected in accordance with the appropriate
connection diagram.
Protection Class I Equipment
Before energizing the equipment it must be earthed using the protective conductor terminal,
if provided, or the appropriate termination of the supply plug in the case of plug connected
equipment.
The protective conductor (earth) connection must not be removed since the protection
against electric shock provided by the equipment would be lost.
The recommended minimum protective conductor (earth) wire size is 2.5 mm² or as per
industries standard practice. The protective conductor (earth) connection must be of low-
inductance and as short as possible.
All connections to the equipment must have a defined potential.
Before energizing the equipment, the following points should be checked:
•
Voltage rating / polarity (rating label / equipment documentation);
•
CT circuit rating (rating label) and integrity of connections;
•
Integrity of the protective conductor (earth) connection (where applicable);
•
Voltage and current rating of external wiring, applicable to the application.
Accidental touching of exposed terminals
If working in an area of restricted space, such as a cubicle, where there is a risk of electric
shock due to accidental touching of terminals which do not comply with IP20 rating, then a
suitable protective barrier should be provided.
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......