Doc ID : ADR111A_IM_01
Ref ID : ADR111A/IM/I&P
Rev No. : 04
Page No. : 36 of 127
ADR111A /
ADR211A
more than two rings per terminal. The product is supplied with sufficient M4 screws for
proper connection.
M4 Terminal block for CT connection, Auxiliary Supply, Output connection
Figure 6: Terminal blocks
Caution: Always fit an insulating sleeve over the ring terminal.
2.3.8
Rear Serial Port connection (For ADR211A only)
The rear serial port is intended for use with a permanently wired connection to a remote
SCADA system. The physical connectivity is achieved using four terminals A5-A6-A7-A8 for
signal connection shown below.
For connecting the RS422, use screened cable with a maximum total length of 1000 m or
200 nF total cable capacitance.
A typical cable specification would be:
Each core: 16/0.2 mm2 copper conductors, PVC insulated
Nominal conductor area: 0.5 mm2 per core
Screen: Overall braid, PVC sheathed
There is no electrical connection of the cable screen to the device. The link is provided
purely to link together the two cable screens.
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......