SETTING SHEET
6.1
Relay Settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 – 9999
This setting specifies to enter the set password
2.
New Password
0000
0000 – 9999
This setting specifies to set the new password
3.
Unit ID
001
001 – 250 in step of 1
This cell sets the unique address for the relay such that only one relay is accessed by master station
software.
4.
I>
100%
5% – 250% in step of 1%
This setting determines Pick-up setting for first stage (IDMT/DT) over current element.
5.
I> TMS
1.00
0.01 – 1.50 in steps of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
6.
I>>
100%
50% – 3000% in step of 1%
This setting determines Pick-up setting for second stage (Inst/DT) over current element.
7.
I> Curve
C1
Normal Inverse 1 (C1)/ Normal Inverse 2
(C2)/ Very Inverse (C3)/ Extremely Inverse
(C4)/ Extremely Inverse (C4A)/ Long Time
Inverse (C5)/ Definite Time (C6)
This setting is used to select the IDMT curves for the various applications.
8.
C6 Time
0 s
0 – 99.9 s in step of 0.1 s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage over
current element.
9.
I>> Delay
1.00 s
0.00 – 10s in steps of 0.01s
This setting is used to set the time-delay for the setting for second stage over current element.
10.
BF Delay
050
000 – 800 ms in step of 50 ms
This setting is used to set the time-delay for the CBF trip.
11.
CT Secondary
1 A
1 A/5 A
This setting is used to set the CT Secondary
12.
CT Primary
10 A
10 – 5000A in step of 1A
This setting is used to set the CT Primary.
13.
Trip Cont
1
001 – 002 (1=SR, 2=HR)
This setting specifies to Trip contact can be set to Manual/Hand reset (HR) or Self reset (SR)
14.
BF Cont
1
001 – 002 (1=SR, 2=HR)
This setting specifies to BF contact can be set to Manual/Hand reset (HR) or Self reset (SR)
15.
Com Port
FRONT
FRONT/REAR
This setting specifies to select communication port for 103 communications.
16.
Parity
None
None/Even/Odd
Summary of Contents for ADR111A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 27: ...Page intentionally Left Blank...
Page 42: ...Page intentionally Left Blank...
Page 52: ...Page intentionally Left Blank...
Page 64: ...Page intentionally Left Blank...
Page 68: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 84: ...Page intentionally Left Blank...
Page 104: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 119: ...Doc ID ADR111A_IM_01 Ref ID ADR111A IM DR Rev No 04 Page No 119 of 127 ADR111A ADR211A...
Page 120: ...Page intentionally Left Blank...
Page 128: ......