LOAD MANAGEMENT, cont.
Voltage Droop
If the yacht’s electrical system does not include a power management system that allows for
automatic load-shed, the converter’s Voltage Droop feature may be used to save up to 10% capacity
by reducing the converter output voltage up to 5% (1% to 5% range). This feature may be enabled or
disabled by the user and droops upon Shore Cord Alarm.
Automatic Transfer to Generator
The converter system may be set to automatically transfer to generator (assuming the existence of the
Seamless Transfer Option) upon Shore Cord Alarm. The Automatic Transfer would only occur after
the Voltage Droop had taken effect if both were enabled. This feature may be enabled or disabled by
the user. A signal generated by the converter may be used to start the selected generator. Also, a
programmable warm-up delay is available.
Summary of Contents for AC100LC-3
Page 42: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 42 This page intentionally left blank ...
Page 62: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 62 11 MSDS SHEET COOLANT OIL ...
Page 63: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 63 11 MSDS SHEET COOLANT OIL cont ...
Page 64: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 64 11 MSDS SHEET COOLANT OIL cont ...
Page 65: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 65 11 MSDS SHEET COOLANT OIL cont ...
Page 66: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 66 11 MSDS SHEET COOLANT OIL cont ...
Page 67: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 67 11 MSDS SHEET COOLANT OIL cont ...
Page 68: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 68 11 MSDS SHEET COOLANT OIL cont ...