ELECTRICAL INSTALLATION, cont.
INPUT WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN FAMILIAR
WITH STANDARD SAFEGUARDS AND PROCEDURES REQUIRED BY THE
INSTALLATION OF THIS TYPE OF EQUIPMENT. POWER MUST BE REMOVED
FROM THE INPUT DISTRIBUTION SYSTEMS SUPPLYING POWER TO THE AC90LC-
3, AC100LC-3, OR AC125LC-3 PRIOR TO THE START OF THE FOLLOWING STEPS.
INPUT POWER MUST BE SECURED (LOCKED) IN THE OFF (DE-ENERGIZED) STATE
UNTIL INSTRUCTED OTHERWISE BY THIS DOCUMENT. ALSO SECURE IN THE
OFF STATE ANY CIRCUIT BREAKER(S) IN THE SWITCHGEAR PANEL THAT MAY
BE SUPPLYING SHIP’S BUS POWER TO THE CONVERTER OUTPUT TERMINAL
BLOCK. FAILURE TO FOLLOW THESE PROCEDURES CAN RESULT IN DAMAGE
TO THE EQUIPMENT, AND CAN PRESENT THE RISK OF INJURY OR DEATH TO THE
INSTALLER OR THE OPERATOR.
5.3.1 Input Power Connections
The converter is supplied with stud type terminal blocks for input power connections. The studs are
3/8-16 UNC and 1.25” long. The recommended torque value is 228 lbf·in, or 25.8 Nm. These
terminal blocks area rated for 400A and 600V maximum. Refer to the applicable standards for
selection of required wire gauge and type. In two or more cabinet systems, one shore cord is
connected to each converter shore power terminal block.
5.3.2 Output Power Connections
The converter is supplied with stud type terminal blocks for output power connections. The studs are
3/8-16 UNC and 1.25” long. The recommended torque value is 228 lbf·in, or 25.8 Nm. These
terminal blocks area rated for 400A and 600V maximum. Refer to the applicable standard for
selection of the required wire gauge and type. The output ground wire is to be connected to a 3/8-16
UNC stud. Please refer to the Figure 7 on page 23 for additional detail.
Summary of Contents for AC100LC-3
Page 42: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 42 This page intentionally left blank ...
Page 62: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 62 11 MSDS SHEET COOLANT OIL ...
Page 63: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 63 11 MSDS SHEET COOLANT OIL cont ...
Page 64: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 64 11 MSDS SHEET COOLANT OIL cont ...
Page 65: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 65 11 MSDS SHEET COOLANT OIL cont ...
Page 66: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 66 11 MSDS SHEET COOLANT OIL cont ...
Page 67: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 67 11 MSDS SHEET COOLANT OIL cont ...
Page 68: ...AC90LC 3 AC100LC 3 and AC125LC 3 Operations Manual 68 11 MSDS SHEET COOLANT OIL cont ...