If a battery isolating point is provided, it must be equipped to handle a current of
20 A (at 12 VDC).
[1]
Primary connector
[2]
Secondary connector
[3]
Cable clamp (Fast-ON 6.3 mm)
[4]
Rubber grommet
[5]
Cable to 12V back-up battery (cable cross-section 4 mm2)
[6]
12V back-up battery (external)
Fig. 32
Connecting the UPS-12V module
Fitting and connecting the UPS-12V module
Hazard:
Be sure to observe the
Note:
When disconnecting a system with a UPS-12V module from the power
supply, the battery must always be first disconnect. When connecting,
always connect the mains voltage first and then the battery.
1.
Disconnect the PBX from the power supply.
2.
Remove the cover of the power supply area.
3.
Mount the angle bracket with the provided screws.
4.
With the jumper on the UPS-12V module, select the required charge current lim-
iting (1 A or 2 A).