USER'S MANUAL
SP-AS/AL Series Switch Power
Operation Steps:
1.
Twist firmly the short circuit block of the switch terminal (If the switch / short-
circuit block is off,the switch power have no output)
2. Adjusting potentiometer (A) and rotate it to the end clockwise
3. Connect the power (100-240VAC/140-340VDC)
4.
Adjusting potentiometer(V) to make the voltage of the output terminal be +24VDC (Due
to SP-12AS/AL to make the output voltage be 12V)
5. Disconnect the AC/DC power wire
6. Connect the switch and fuse wire and the battery according to the positive pole
and negative pole marked on the crust
7. Connect the power (100-240VAC/140-340VDC)(If the battery voltage is over
+24V,you need to adjust potentiometer(V)to make it over battery voltage, the
adjustable voltage is not exceed 26.5V)
Attn:
1. At this time the main output voltage is provided by load: BATT port charges
the accumulator battery by the switch k2 and fuse wire F1; If there is no AC/
DC voltage input, battery power supply the load by the internal circuit, the
Maximum
working current ≤3A
2. At this time the main output voltage provided by load is more 24V.
d. Using Remote Control and UPS simultaneously
Attn: Using remote control and UPS simultaneously, the using method is
combined by the method 2 and method 3 as belows:
112
Summary of Contents for AF-10MR-A2
Page 1: ......
Page 11: ...FAB2 Intelligent Controller MEMO 10...
Page 43: ...FAB2 Intelligent Controller MEMO 42...
Page 57: ...FAB2 Intelligent Controller 56 MEMO...
Page 74: ...FAB2 Intelligent Controller MEMO 73 Fig 1 11 The semoval screen of Quick II...
Page 78: ...FAB2 Intelligent Controller 77 MEMO...
Page 116: ...FAB2 Intelligent Controller MEMO 115...
Page 124: ...FAB2 Intelligent Controller MEMO 123...
Page 126: ...FAB2 Intelligent Controller MEMO 125...
Page 128: ...FAB2 Intelligent Controller 127...
Page 129: ......