2 - Insulating with Arma-Chek D >> Using Pre-Covered Tubes

APPLICATION MANUAL  

 

D

© ARMACELL UK LTD.

Insulating with Arma-Chek D >> Using Pre-Covered Tubes

ARMA-CHEK D PRE-COATED TUBES

 

Arma-Chek D pre-coated tubes are supplied with a self-
adhesive seal in 1 metre lengths. The covering fi nishes 
approximately 10 mm before the end of the tube in order 
to guarantee that the insulation material is installed “un-
der tension” around butt joints.
The Arma-Chek D pre-coated tube range is available for 
pipes with an outer diameter of up to 89 mm. For larger-
sized pipes with an outer diameter of 102 mm up to 160 
mm  special  (non  self-adhesive)  pre-coated  tubes  are 
available on request.

Note:

  Due  to  the  semi-fl exible  nature  of  the  products 

sleeving around bends is not possible!

INSULATING STRAIGHT PIPES (OD < 89 MM)

 

 

1.  Clean  the  pipe  surface  with  Armafl ex  cleaner 
   removing any dust or other contamination.
2.  Snap the tube onto the pipe.

 

 

3.  Peel  back  both  release  paper  strips  step  by  step, 
   200 mm at a time. Align the seam joints and apply 
   heavy pressure to the complete seam, this action will 
   allow closure.

   Note: 

Always check the seam is fully bonded before 

   proceeding to the next steps.
4.  Lay the covering tightly round the tube and fi x using 
   the factory applied adhesive strip.
5.  Use  correct Armafl ex  adhesive  to  secure  the  longi-
   tudinal  seam.    Apply  on  one  side  only.  Always 
   remember to “stagger” longitudinal seams.
6.  Secure the butt end on the under face of the Armafl ex 
   tube with the Armafl ex adhesive and also provide a 
   “wet seal“ to the adjoining tube.
7.  

For internal application:

   The  butt  joints  have  to  be  over  secured  with  the 
   matching  50mm  width  self-adhesive  Arma-Chek  D 
   tape.

   

50 mm

 

   

For external application:

   Over seal all seam and jointing details of the covering 
   with  a  “bead”  of Arma-Chek  Black  or  Grey  Mastic. 
   Ensure all joints are staggered away from the direct 
   patch of rain, provide a watershed.
8.  Use  the  Arma-Chek  mastic  to  seal  all  seams  and 
   joints! All seams and joints to have an allowance of a 
   min. of 10 mm wide and 3 mm thick mastic “beading” 
   applied.

USING THE ARMAFLEX TEMPLATE 

The fabrication of bends and tees using Armafl ex tube 
requires tubes to be cut to different angles. In order to 
make this process quicker and easier, the Armafl ex tem-
plate is provided on every box of Armafl ex.  
Additional copies are available on request (contact your 
local Armacell representative for more information). 
1.   Place a copy of the Armafl ex template face up on a 
     table or worktop. 
2.   Line a tube of Armafl ex across the template parallel 
     along the horizontal base line. 
3.   Select the required angle cut from the template and 
     cut along this line.

D (5)

Summary of Contents for Arma-Chek D

Page 1: ...application manual ARMA CHEK D application manual application manual ARMA CHEK D D...

Page 2: ...application manual ARMA CHEK D ARMACELL UK LTD D APPLICATION MANUAL D...

Page 3: ...ways use the correct speci ed Arma ex adhesives Do not assume they will always do the same job If in doubt consult the Armacell technical department local agent On external installations always ensure...

Page 4: ...ntire surface smoothing the covering round making sure there are no air pockets present Always check for alignment and avoid creases and crinkles during that time e If the surfaces are left to dry too...

Page 5: ...clean the seams and joints use the Arma ex cleaner Peel back release paper and cover the entire seam line with an additional 50 mm overlap where appli cable applying pressure during the installation C...

Page 6: ...General Working with Arma Chek D ARMACELL UK LTD D APPLICATION MANUAL 1 General Working with Arma Chek D 4 D...

Page 7: ...d x using the factory applied adhesive strip 5 Use correct Arma ex adhesive to secure the longi tudinal seam Apply on one side only Always remember to stagger longitudinal seams 6 Secure the butt end...

Page 8: ...seam of the throat using 20 mm wide Arma Chek S Butyl Tape Always ensure the tape is applied such that a watershed is achieved Note In some circumstances it may be preferable to fabricate segment ttin...

Page 9: ...ARMAFLEX TUBE Note Yellow lines indicate where cuts are to be made Always follow instructions related to the application of pre coated Arma Chek S tubes as stated in the above procedures relating to a...

Page 10: ...over the tting The oversize tting should extend by the wall thickness of the over sized fabrication minimum of 25 mm is required over the adjoining insulation On the butt end of the adjoining insulat...

Page 11: ...ness 1 mm 1 This table is valid for ambient conditions of 5 C For lower applica tion temperatures the rigidity and tension of the sheet material can increase thus lead ing to other conditions than men...

Page 12: ...e by drawing the half elevation on the edge of the Arma Chek sheet 4 Completed Arma Chek pipe reducer made of factory coated Arma Chek Dsheet material with a straight nish ECCENTRIC REDUCER FLAT BACK...

Page 13: ...meter of the connected pipes 2 x ins thickness Note 5 mm must be added to the jacket height deter mined 5 mm must be subtracted from all measur ments for openings 2 Cross section A A Determine the cir...

Page 14: ...borders directly on the ange with a 100 mm wide strip of Arma ex Determine the dimensions of the ductwork surface to be insulated On bends the inner throat and outer dimensions are determined using st...

Page 15: ...HANGING DUCTWORK Use the Arma x duct supports to optimize the preven tion of thermal bridging and simplify the hanging of duct work VESSELS 1 First insulate the vessel jacket with Arma Chek D pre coat...

Page 16: ...Insulating with Arma Chek D Using Pre Covered Sheets ARMACELL UK LTD D APPLICATION MANUAL 3 Insulating with Arma Chek D Using Pre Covered Sheets 14 D...

Page 17: ...are no gaps present in all the seams and joints Note Refer to the Arma ex Installation Manual at all times 2 For Arma Chek D covering adhesive is only required on the Arma ex and on the overlapping ar...

Page 18: ...ongitudinal seam of the covering with the correct Arma ex adhesive Continue to install the covering along the ductwork allowing for a 50 mm overlap on all butt joints DUCTWORK BENDS IRREGULAR SHAPES 1...

Page 19: ...seg ment of the assembled segment bend and determine the circumference 2 Transfer the circumference measurement U to the Arma Chek Dcovering material and draw in a line dividing it in half Now add a 5...

Page 20: ...pipe and transfer this to the covering material Halve the circumference 3 Transfer segment width for the throat seam to each end of the circumference drawn and the segment width for the back of the be...

Page 21: ...a pair of scissors OFFSET ANGLES 1 Determine the circumference U of the Arma ex in sulated offset angle the maximum a and minimum b height and the Arma ex insulated outer diameter of the pipe D to wh...

Page 22: ...material to the insulation material Secure the seams with Arma Chek D self adhesive tape on indoor applications with 100 mm wide strips of the covering material applied with all over adhesive coverag...

Page 23: ...eathering overlap length minimum equal to the insulation thickness of the non covered area Method 2 1 Measure the following diameters of the end cap a smaller insulated outer diameter of insulated bod...

Page 24: ...ARMACELL UK LTD D APPLICATION MANUAL 4 Covering Using Arma Chek D Covering Covering Of Insulated Objects Using Arma Chek D Covering 22 D...

Page 25: ...application manual ARMA CHEK D ARMACELL UK LTD APPLICATION MANUAL D D...

Page 26: ...ightweight and easy to apply insulation system resistant to mechanical impact D D Arma Chek R The insulation system with extra system security that minimises the risk of under insulation corrosion UIC...

Reviews: