background image

4 - Covering  >> Using Arma-Chek D Covering

APPLICATION MANUAL   

 

D

© ARMACELL UK LTD.

Covering Of Insulated Objects >> Using Arma-Chek D Covering

VALVE NECK-T / PIPE-T

1.  Determine  the  circumference  of  the Armafl ex  insu-
   lated T-branch.
2.  Transfer  the  circumference  measurement  on  the 
   Arma-  Chek  covering  and  mark  the  circumference 
   into 4 equal sections. Add an additional 50 mm over-
   lap on one side of this section.

   

  

3.  Measure  the  minimum  height  (a)  of  the  insulated 
   T-branch.  Transfer  these  height  to  the  marked  out 
   covering.
4.  Measure  the  outer  diameter  of  the  insulated  main 
   pipe. Take  the  half  of  this  measurement  (radius  r  ) 
   with a pair of dividers, mark out 2 arcs round the inter
   sections  of  the  second  and  forth  line  touching  the 
   termination point of (a). Take the same measurement 
   (radius r) and mark out three arcs around the inter
   sections 1, 3 and 5 touching the fi rst two arcs. That 
   leads to joined arcs with a continuous line.

5.  Add an additional 10 mm overlap to allow for ”feather-
   ing“ on the master pattern. Cut the pattern out with a 
   pair of scissors.

OFFSET ANGLES

1.  Determine the circumference (U) of the Armafl ex in-
   sulated offset angle, the maximum (a) and minimum 
   (b) height, and the Armafl ex insulated outer diameter 
   of the pipe (D) to which the offset angle connects.
2.  Transfer the circumference (U) to the Arma-Chek D 
   covering material. Halve the circumference.

   

  

3.  Mark the minimum height (b) of the offset angle on 
   the halving line and thus determine the termination 
   point B. Mark the maximum height (a) on each of the 
   side  lines  and  thus  determine  the  termination  point 
   A.
4.  Draw a circle which stands vertically on point B and 
   only touches it at one point (note: if the halving line is 
   extended it runs through the centre of the circle). The 
   diameter  of  the  circle  is  a  quarter  diameter  of  the 
   Armafl ex insulated diameter of the main pipe (D).

   

 

5.  Add an overlap of 50 mm to one side.
6.  Draw the jacket line by marking two arcs (radius = half 
   circumference) between a tangent of the circle stand-
   ing on termination point B and the termination points 
   A (continue the arc into the 50 mm overlap).

   

  

7.  When using the feathering technique it is necessary to 
   allow at least 10 mm parallel to the jacket line. Cut out 
   the pattern using a pair of scissors or craft knife.

   

  

D (19)

Summary of Contents for Arma-Chek D

Page 1: ...application manual ARMA CHEK D application manual application manual ARMA CHEK D D...

Page 2: ...application manual ARMA CHEK D ARMACELL UK LTD D APPLICATION MANUAL D...

Page 3: ...ways use the correct speci ed Arma ex adhesives Do not assume they will always do the same job If in doubt consult the Armacell technical department local agent On external installations always ensure...

Page 4: ...ntire surface smoothing the covering round making sure there are no air pockets present Always check for alignment and avoid creases and crinkles during that time e If the surfaces are left to dry too...

Page 5: ...clean the seams and joints use the Arma ex cleaner Peel back release paper and cover the entire seam line with an additional 50 mm overlap where appli cable applying pressure during the installation C...

Page 6: ...General Working with Arma Chek D ARMACELL UK LTD D APPLICATION MANUAL 1 General Working with Arma Chek D 4 D...

Page 7: ...d x using the factory applied adhesive strip 5 Use correct Arma ex adhesive to secure the longi tudinal seam Apply on one side only Always remember to stagger longitudinal seams 6 Secure the butt end...

Page 8: ...seam of the throat using 20 mm wide Arma Chek S Butyl Tape Always ensure the tape is applied such that a watershed is achieved Note In some circumstances it may be preferable to fabricate segment ttin...

Page 9: ...ARMAFLEX TUBE Note Yellow lines indicate where cuts are to be made Always follow instructions related to the application of pre coated Arma Chek S tubes as stated in the above procedures relating to a...

Page 10: ...over the tting The oversize tting should extend by the wall thickness of the over sized fabrication minimum of 25 mm is required over the adjoining insulation On the butt end of the adjoining insulat...

Page 11: ...ness 1 mm 1 This table is valid for ambient conditions of 5 C For lower applica tion temperatures the rigidity and tension of the sheet material can increase thus lead ing to other conditions than men...

Page 12: ...e by drawing the half elevation on the edge of the Arma Chek sheet 4 Completed Arma Chek pipe reducer made of factory coated Arma Chek Dsheet material with a straight nish ECCENTRIC REDUCER FLAT BACK...

Page 13: ...meter of the connected pipes 2 x ins thickness Note 5 mm must be added to the jacket height deter mined 5 mm must be subtracted from all measur ments for openings 2 Cross section A A Determine the cir...

Page 14: ...borders directly on the ange with a 100 mm wide strip of Arma ex Determine the dimensions of the ductwork surface to be insulated On bends the inner throat and outer dimensions are determined using st...

Page 15: ...HANGING DUCTWORK Use the Arma x duct supports to optimize the preven tion of thermal bridging and simplify the hanging of duct work VESSELS 1 First insulate the vessel jacket with Arma Chek D pre coat...

Page 16: ...Insulating with Arma Chek D Using Pre Covered Sheets ARMACELL UK LTD D APPLICATION MANUAL 3 Insulating with Arma Chek D Using Pre Covered Sheets 14 D...

Page 17: ...are no gaps present in all the seams and joints Note Refer to the Arma ex Installation Manual at all times 2 For Arma Chek D covering adhesive is only required on the Arma ex and on the overlapping ar...

Page 18: ...ongitudinal seam of the covering with the correct Arma ex adhesive Continue to install the covering along the ductwork allowing for a 50 mm overlap on all butt joints DUCTWORK BENDS IRREGULAR SHAPES 1...

Page 19: ...seg ment of the assembled segment bend and determine the circumference 2 Transfer the circumference measurement U to the Arma Chek Dcovering material and draw in a line dividing it in half Now add a 5...

Page 20: ...pipe and transfer this to the covering material Halve the circumference 3 Transfer segment width for the throat seam to each end of the circumference drawn and the segment width for the back of the be...

Page 21: ...a pair of scissors OFFSET ANGLES 1 Determine the circumference U of the Arma ex in sulated offset angle the maximum a and minimum b height and the Arma ex insulated outer diameter of the pipe D to wh...

Page 22: ...material to the insulation material Secure the seams with Arma Chek D self adhesive tape on indoor applications with 100 mm wide strips of the covering material applied with all over adhesive coverag...

Page 23: ...eathering overlap length minimum equal to the insulation thickness of the non covered area Method 2 1 Measure the following diameters of the end cap a smaller insulated outer diameter of insulated bod...

Page 24: ...ARMACELL UK LTD D APPLICATION MANUAL 4 Covering Using Arma Chek D Covering Covering Of Insulated Objects Using Arma Chek D Covering 22 D...

Page 25: ...application manual ARMA CHEK D ARMACELL UK LTD APPLICATION MANUAL D D...

Page 26: ...ightweight and easy to apply insulation system resistant to mechanical impact D D Arma Chek R The insulation system with extra system security that minimises the risk of under insulation corrosion UIC...

Reviews: