v2.00
Ariterm Oy
21.5.2013
29
Underpressure at effect
run
25Pa
0-100Pa
Underpressure setting when
burner is in effect mode.
Underpressure alarm
limit
-20Pa
-
100…0Pa
Combustion chambers
overpressure limit reached,
followed by "Alarm! Smoke gas
fan". NOTE! Limits should be set
with a negative marker (-).
Underpressure scaling
min.
-100Pa
-
100…100Pa Pressure sensor scaling. NOTE!
Requires Maintenance level
password.
Underpressure scaling
max.
100Pa
-
100…100Pa Pressure sensor scaling. NOTE!
Requires Maintenance level
password.
The speed of the smoke gas fan is regulated according to the underpressure
of the combustion chamber. Underpressure can be set for the
Upkeep
and
Effect
modes.
By pressing the TREND/PID -button, you can review the smoke gas fan
adjustments. The underpressure should remain approximately same as the
set value. If the smoke gas fan adjustment wavers, its speed can be adjusted
with the
Gain (P)
and
Integration time (Ti)
-settings.
17.
Accessories
17.1 Bar discharger
Figure 17. BAR DISCHARGER settings.
Start delay
120s
0-360s
When the storage auger has run