Figure 8. Manual ignition -page - Burner equipped with automatic ignition.
Run the burner auger with the BURNER SCREW -button so that the burner
head has enough fuel. The storage auger automatically fills the funnel while
the smoke gas fan maintains an underpressure in the combustion chamber.
Ignite the fuel and turn on combustion air fans. Wait for the fuel to properly
ignite. You can add more fuel to the burner head. When the flame is large
enough, the
Ignition 1
-phase can be acknowledged with the MANUAL
IGNITION 2 -button, after which the system will proceed to the
Ignition 2
-
phase.
During the
Ignition 2
-phase, the burner is run at a fixed effect level, which the
user can adjust. In this case, the fuel feed and fanning is controlled
automatically.
NOTE!
During the first heating process, the burner should
be run at low power (21-30%) for approximately one hour in order to
remove humidity from the burner ceramics.
When the flame detection
detects a flame, a flame symbol will be displayed
. Then you can activate
automatic effect adjustment by pressing the MAN. IGNITION READY -button.
You do not need to wait for the flame information. The
Ignition 2
can be
acknowledged earlier as well.
The flame information is provided by the flame detection thermostat
measuring the temperature of smoke gas. When the smoke gas temperature
exceeds the thermostat limit (approximately 70°C), the flame information is
displayed. The flame detection phase (10 min.) is activated after the
Ignition
2
-phase. During this phase, the smoke gas temperature increases over the
set temperature.
If the system is equipped with automatic ignition, the flame data is monitored
during the ignition with an optical flame detection sensor.