v2.00
Ariterm Oy
21.5.2013
27
15.
Storage auger settings
Figure 15. STORAGE AUGER settings
Setting
Factory
setting
Setting
frequency
Function
Funnel's emptying time
15s
0-60s
When the funnel photocell pair no
longer detects fuel in the funnel,
the total operating pulse time of the
burner screw is calculated. When
the set time is reached, the storage
auger is activated. The settings
define the lower limit of the funnel.
When the photocell pair detects
fuel, the storage auger stops.
Storage alarm time delay
600s
0-1200s
When the storage auger has run
for the set time, but the funnel
photocell pair fails to detect the
surface of the fuel, the system
indicates the
Alarm!
Fuel low
alarm.
Inactive sensor level for
burner screw
150s
0-600s
If the funnel photocell pair detects
fuel during the set time (calculated
with the feeder auger pulses), the
storage auger is activated for the
set duration. The purpose here is
to remove any splinters blocking
the sensor. NOTE! Settings are
displayed if the bar discharger
option was selected.
Funnel's force filling
time
2s
0-60s
Storage auger running time after
the forced filling delay.